Air conditioning and air distribution
Noise and vibration
Noise complaints arrive after handover, when the cheap fixes have gone. How to read sound data, where HVAC noise starts, what attenuators and acoustic materials actually do, and how to mount plant so it stays quiet and stays put in an earthquake.
10⁻¹² WReference for sound power level; sound pressure level uses 20 µPa
NC 30–35Typical noise criterion for quiet offices and meeting rooms
25 / 50 mmCommon static deflections of spring isolators for plant on floors and roofs
Reading sound data
Sound power and sound pressure
- Sound power is a property of the source and does not change with distance or room; compare products on it.
- Sound pressure is what you hear at a point and depends on distance, reflections and the room.
- Data quoted as dB re 10⁻¹² W in octave bands from 63 Hz to 8 kHz is sound power.
Adding and comparing
- Two equal sources add 3 dB; ten equal sources add 10 dB.
- A 10 dB drop sounds about half as loud.
- Low frequencies (63–250 Hz) are the hardest to attenuate and travel through structures.
Design targets
- Set room targets as NC or dB(A): bedrooms and meeting rooms lower, open-plan offices higher.
- Check boundary noise at neighbours against the district plan, which is often stricter at night.
- Schools and some buildings have their own acoustic standards.
Where HVAC noise comes from
Sources
- Fans, compressors and pumps at the plant.
- Air regenerated noise at fittings, dampers and grilles when velocity is too high.
- Breakout through thin duct walls near the fan.
- Crosstalk between rooms through shared ductwork.
Fixes in order of cost
- Select a quieter fan near peak efficiency, at lower speed.
- Lower duct and grille velocities.
- Add attenuators, lined duct or plenums.
- Enclose or relocate the plant.
Attenuators and acoustic materials
Attenuators
- Rectangular splitter and circular podded attenuators absorb sound in mineral wool or glass fibre infill.
- Compare insertion loss in each octave band, not just one number.
- Every attenuator adds pressure loss; include it in the fan duty (often 30–80 Pa).
- Crosstalk attenuators go in transfer paths between private rooms.
Materials
- Mineral wool (rock or slag wool) is non-combustible and absorbs sound and heat.
- Infill is wrapped in a thin film and faced with perforated galvanised sheet so fibres do not enter the airstream.
- Acoustic louvres: check pressure loss and insertion loss, not only free area.
- Acoustic doors are rated by Rw sound reduction, fire integrity and the perimeter seals.
Vibration isolation and seismic restraint
Isolators
- Rubber pads and mounts suit small fans and pumps on solid floors.
- Spring isolators with 25 mm or 50 mm deflection suit larger plant and lightweight floors or roofs.
- Use flexible connections on ducts and pipes so vibration does not bypass the isolators.
Seismic restraint
- Plant, ducts and pipes must be restrained for earthquakes to NZS 4219 in New Zealand.
- Spring isolators need seismic-rated housings or snubbers so the plant cannot jump off them.
- The restraint design usually comes with a producer statement from an engineer.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.