Air conditioning and air distribution
Duct design
Duct that is too small costs fan power for the life of the building; duct that is too big takes ceiling space nobody gave you. Sizing methods, the velocity limits that keep a system quiet, standard sizes and pressure classes, and how to total the pressure the fan has to beat.
Ductulator
Size a duct against a velocity limit and a friction limit at the same time, in metric or inch-pound units. Rigid galvanised duct and flexible duct are not the same pipe, so pick the material before you read the answer.
It solves the Colebrook-White friction factor and uses the ASHRAE circular equivalent De = 1.30 (ab)^0.625 / (a+b)^0.25 for rectangular ducts, so the figures line up with a printed duct calculator. Velocity shown is the real velocity in the duct, which is the one that matters for noise. This sizes straight duct only: bends, takeoffs, dampers and the unit itself still have to be added up.
Sizing methods
Equal friction
- Pick one friction rate (about 1 Pa per metre for low-pressure commercial work) and size every section to it with a duct calculator.
- Simple and fast, and the usual method for supply and return systems in offices, schools and retail.
- Long runs end up with more pressure loss than short ones, so balance with dampers.
Static regain and even pressure
- Size so the static pressure at each branch is about the same, which suits long trunks and VAV systems.
- The aim is a low, even static pressure across all terminals, not a fixed friction rate.
- Even pressure is not the same as a constant-pressure control strategy; it is a sizing approach.
Adding up fittings
- For the index run (the path with the highest resistance), list every straight length, bend, tee, transition and damper.
- Take loss coefficients from the ASHRAE Duct Fitting Database and multiply by the velocity pressure.
- Add equipment losses from data sheets: filters (at their dirty value), coils, heaters, attenuators, fire dampers and grilles.
- The total is the external static pressure the fan must deliver at the design airflow.
Velocity limits
| Duct | Quiet spaces | General commercial | Notes |
|---|---|---|---|
| Main supply | 4–5 m/s | 5–6 m/s | Higher velocity means smaller ducts but more noise and pressure loss. |
| Branch | ≤4 m/s | 4–5 m/s | Slow down near diffusers to keep regenerated noise low. |
| Flexible duct | ≤3 m/s | 3–3.5 m/s | Flex has more friction and noise than rigid duct; keep runs short and straight. |
| Return | 4–5 m/s | 5–6 m/s | Can run a little faster than supply because it is further from people. |
| Kitchen exhaust | – | 7.6–10 m/s | Keeps grease and dust from settling in the duct. |
Sizes worth remembering
Round duct
- Common diameters: 100, 125, 150, 200, 250, 315, 355, 400, 450, 500, 560 and 630 mm. 315 is now more common than 300 on new work.
- At about 3 m/s: 100 mm ≈ 24 L/s, 150 mm ≈ 53 L/s, 200 mm ≈ 94 L/s, 250 mm ≈ 147 L/s, 300 mm ≈ 212 L/s, 400 mm ≈ 377 L/s.
- Airflow (L/s) = velocity (m/s) × area (m²) × 1000.
Flexible duct to a diffuser (rule of thumb)
- Up to 50 L/s: 150 mm
- 51–100 L/s: 200 mm
- 101–200 L/s: 250 mm
- 201–250 L/s: 300 mm
- 251–350 L/s: 350 mm
- 351–450 L/s: 400 mm
Rectangular duct
- Use the equivalent diameter (Huebscher) to compare a rectangular duct with a round one of the same friction.
- Keep the aspect ratio below about 4:1; flat ducts cost more sheet metal and lose more pressure.
- The duct sizer in the HVAC Quote Playbook does both conversions.
Duct types and materials
Nearly every commercial job is galvanised steel, and nearly every argument is about the bits that are not. The material decides the roughness, the leakage class, how it is cleaned and whether it survives what is inside it.
| Type | What it is | Where it suits | Watch for |
|---|---|---|---|
| Rectangular galvanised | Folded sheet steel with cleated or flanged joints, stiffened on the flats | The default where ceiling depth is tight and the shape has to suit the space | Leakage and drumming at the flats; it uses more metal and more sealant per litre than round |
| Spiral round | Machine-wound strip, with sealed slip or coupling joints | Anywhere you can give it the height: stiffer, tighter and lower friction than rectangular | Fittings cost more and take longer, and the sizes are fixed steps |
| Flat oval | A round duct squashed, keeping most of the stiffness in less depth | The compromise when round will not fit but you want its behaviour | |
| Flexible | A wire helix in a plastic or foil sleeve, usually with an insulation blanket over it | The last short connection to a diffuser, and nothing else | Pressure loss several times rigid duct when compressed, which is the usual reason a house system underperforms |
| Semi-rigid radial tube | Smooth-bore plastic or aluminium tube, run one per valve from a manifold | Heat recovery systems in houses: easy to balance, easy to clean | Every run should be a similar length, or balancing becomes guesswork |
| Rigid fibreglass duct board | Preformed insulating board cut and taped into duct | Low-cost insulated duct in dry, clean, low-pressure systems | The air side is the insulation: it erodes, it holds dirt, and it cannot be cleaned hard |
| Pre-insulated panel | Phenolic or PIR panel with foil facings, cut and assembled on site | Retrofits and tight ceilings: insulation and duct in one thickness, and light to handle | Joint quality is everything, and it needs fire and smoke properties checked for the application |
| Fabric / textile | A hung fabric sock that distributes air through its weave or through orifices | Food, sport and industrial halls: even low-velocity distribution, and it washes | It needs a minimum pressure to stay inflated, and it drops when the fan stops |
| Stainless steel | Usually 304, or 316 where chlorides are in play | Kitchen grease duct, laboratory exhaust, clean rooms, wash-down areas | Cost, and that welded grease duct is a different trade from sheet metal |
| PVC, polypropylene and FRP | Plastic or fibreglass duct for air that eats steel | Plating, wastewater, laboratory fume, pool halls | Fire performance and support spacing: plastic sags and burns differently from steel |
| Welded grease duct | Continuously welded, liquid-tight, falling back to the hood or a drain point | Commercial kitchen exhaust, where the duct is part of the fire risk | Access panels at every change of direction, and a cleaning regime that actually happens |
| Fire-rated duct | Purpose-made or board-wrapped duct that keeps working, or keeps fire out, for a rated period | Smoke spill, stair pressurisation and any duct crossing a fire compartment without a damper | The rating belongs to the tested system, including supports and penetrations, not to the board alone |
Two numbers follow from the material and the build, not from the size: the roughness, which the Ductulator above lets you change, and the leakage class, which decides how much of the air you paid to move never reaches the room. On a large system an untested leakage class is a bigger number than most of the fittings you argued about.
Construction and pressure classes
Standards
- AS 4254.1 (flexible duct) and AS 4254.2 (rigid duct) in Australia and New Zealand; SMACNA is often quoted for detail.
- Galvanised sheet to AS 1397; keep the zinc coating intact and repair cut edges.
- Flanged joints with a slide-on flange system; cross-break or bead larger panels so they do not drum.
Pressure classes (a common split)
- Low pressure: fan static below about 750 Pa.
- Medium pressure: about 750–1500 Pa.
- High pressure: about 1500–2500 Pa.
- Higher classes need heavier gauge, tighter sealing and leakage testing; check the project specification.
Fittings
- Bend centreline radius at least equal to the duct width; use turning vanes where it cannot be.
- Branch with 45° shoe or bellmouth take-offs rather than square tees.
- Leave straight duct before and after fans, dampers and attenuators so the airflow is even.
Quick airflow estimates for houses
Early-stage numbers for ducted heat pumps before a room-by-room load calculation. Check them against the heat load and the unit data.
| Mode | Air changes | Per floor area | Per kW |
|---|---|---|---|
| Heating | about 5.5 per hour | about 4 L/s per m² | about 33 L/s per kW |
| Cooling | about 12 per hour | about 8.7 L/s per m² | about 72 L/s per kW |
| Evaporative cooling | about 30 per hour | about 22 L/s per m² | about 180 L/s per kW |
Supply airflow (L/s) = room length × width × height (m) × air changes per hour ÷ 3.6.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.