Auxuro

Controls and electrical

Variable speed drives (VSD)

Every maker has much the same functions under different names and different parameter numbers. Who builds HVAC drives and what each is known for, the parameters you set on every job with their numbers on ABB, Siemens, Danfoss and Yaskawa, and the built-in logic each one calls something else: adaptive programming, free function blocks, Smart Logic Controller.

20–50%Typical fan and pump energy saving from running slower instead of throttling (fan laws: power falls with speed cubed)
≈20 blocksA typical size of built-in drive logic: enough for interlocks, timers and alarms, not a full PLC
BACnet MS/TPBuilt into most HVAC drives with Modbus RTU, so the BMS reads kW, kWh, faults and run hours over one cable

Drive makers

MakerFounded and baseHVAC drive rangeKnown forBuilt-in logic
ABBABB formed 1988 (ASEA 1883, Brown Boveri 1891), SwitzerlandACH580, ACH480Widely ranked the largest drives maker; HVAC versions with BACnet, fire mode and pump and fan assistantsAdaptive programming
Siemens1847, GermanySINAMICS G120P, G120X, G120Industry and infrastructure; fits with Desigo BMS and Siemens PLCsFree function blocks (FFB) wired with BICO; DCC on higher control units
Danfoss DrivesDanfoss 1933, Denmark; first mass-produced VLT drive 1968; bought Vacon (Finland) in 2014VLT HVAC Drive FC 102, VACON 100 FLOWDrives-only business; strong in HVAC, water and marineSmart Logic Controller (SLC); VACON Programming (IEC 61131-3)
Schneider Electric1836, FranceAltivar Process ATV630, ATV650; ATV212Building, water and pumping; sold as Square D in North AmericaATV Logic function blocks in SoMove
Yaskawa1915, JapanHV600 (replaced Z1000)Largest Japanese drives maker; big in US HVAC; BACnet, Metasys N2 and APOGEE built inDriveWorksEZ
Rockwell Automation (Allen-Bradley)1903, USAPowerFlex 525, 755Industrial plants running Logix PLCsDeviceLogix
Mitsubishi Electric1921, JapanFR-F800Fans and pumps across AsiaBuilt-in PLC function (GX Works)
Invertek Drives1998, UK; now part of Sumitomo Heavy IndustriesOptidrive EcoCompact drives, common inside packaged AHUs and pump setsOptiTools Studio PLC function blocks
Nidec Control Techniques1973, UK; Nidec since 2017Commander, Unidrive MIndustrial and machine controlOnboard PLC (Machine Control Studio)
WEG1961, BrazilCFW500, CFW11Motors and drives sold together at good pricesSoftPLC
Delta Electronics1971, TaiwanCP2000, C2000Low-cost drives with many featuresBuilt-in PLC

Market lists differ between reports; ABB, Siemens, Danfoss, Schneider and Yaskawa appear at the top of most. In NZ and Australian buildings you mostly meet ABB, Danfoss, Siemens and Schneider, plus whatever drive the AHU or pump maker fitted.

Same setting, different parameter number

SettingABB ACH580Siemens G120X / G120PDanfoss FC 102Yaskawa HV600
Motor nameplate99.06–99.10p0304–p03111-20 – 1-25E1, E2
Motor identification run99.13p19001-29 AMAT1 auto-tuning
Application macro96.04p0015Quick menu Q3A1-06
Control mode (vector or V/f)99.04p13001-01A1-02
Start and stop source20.01p08405-1* and 8-01b1-02
Speed or frequency reference22.11 / 28.11p1000 / p10703-15b1-01
Minimum and maximum speed30.11–30.14p1080 / p10824-11 – 4-14d2-01 / d2-02
Acceleration and deceleration23.12 / 23.13 or 28.72 / 28.73p1120 / p11213-41 / 3-42C1-01 / C1-02
Flying start (catch a spinning fan)21.01p12001-73b3-01
Fault auto-reset31.12–31.15p121014-20L5-01
Analog input scaling12.17–12.20p0756–p07606-1*H3-xx
Analog output13.12p07716-5*H4-01
Relay outputs10.24 / 10.27 / 10.30p0730–p07325-40H2-01
Process PID40.xxp2200–p228520-**b5-xx
Sleep (hibernation)40.43 / 40.44Hibernation, p239822-4*b5-15
Fire mode or override70 OverrideEssential service mode, p388024-0*Fire mode input, H1
Fieldbus protocol58.01p20308-30H5-xx
Actual values (speed, current, kW, DC bus)01.xxr0021–r003916-**U1-xx
Faults and alarm log04.xxr0945 / r212215-3*U2 / U3
Save or factory reset96.06 / 96.07p0971 / p097014-22A1-03

Numbers shift between firmware versions and between the HVAC and industrial variants of the same drive. Use these to find your way in the manual, then confirm against the firmware manual for the exact drive.

ABB parameter groups at a glance

Parameter groupGroup nameWhat you look at or set
01Actual valuesSpeed, frequency, current, kW, torque, DC bus voltage, kWh, PID feedback
03Input referencesReferences received from I/O, the fieldbus adapter or embedded fieldbus
04Warnings and faultsActive fault, active warnings and the fault log
05DiagnosticsOn-time, run time, fan run time, inverter temperature
06Control and status wordsMain control word, main status word, start inhibit reasons
07System infoDrive rating, firmware name and version
10–15I/ODI status, relay sources, DIO, AI and AO scaling, extension modules
19–23Operation, start and stop, speed reference and rampsExt1 and Ext2, run enable, start interlocks, start and stop modes, constant speeds, ramps
28Frequency reference chainThe same as group 22 and 23 for scalar (frequency) control
30LimitsMinimum and maximum speed and frequency, current and torque limits
31Fault functionsExternal events, fault reset, auto-reset, phase loss, earth fault, stall
32SupervisionThree supervision functions that watch any signal against limits and act
40Process PID set 1Setpoint, feedback, gain, integration time, sleep and wake-up
58Embedded fieldbusBACnet MS/TP or Modbus RTU address, baud rate and comms-loss action
70OverrideFire mode speed and source, faults that are ignored
76MultipumpPump staging, alternation and run-time balancing
96 / 99System and motor dataMacro, save and restore; motor nameplate, control mode, ID run

Built-in drive logic

Every maker lets you add a little logic inside the drive so it can run safely without a PLC. Each one has its own name and editor, but they all have the same parts: logic gates, comparators, timers, counters, switches and maths, wired to drive signals, inputs and outputs.

MakerLogic toolHow it is programmed
ABBAdaptive programmingGraphical blocks in Drive Composer or on the panel; a sequence program with states for step logic
SiemensFree function blocks (FFB), BICOBlocks are enabled, given a run-time group, then joined by setting one parameter to another’s output (BICO); DCC for larger charts
DanfossSmart Logic Controller (SLC), group 13Up to 20 steps of event then action, with comparators, timers, logic rules and flip-flops
VaconVACON ProgrammingIEC 61131-3 languages; needs training and the PC tool
SchneiderATV LogicFunction blocks in SoMove that can be exported and reused
YaskawaDriveWorksEZDrag-and-drop block editor on a PC
RockwellDeviceLogixBoolean and function-block logic inside PowerFlex drives
OthersBuilt-in PLC, SoftPLC, OptiTools Studio, onboard PLCMitsubishi, Delta, WEG, Invertek and Control Techniques run small PLC programs in the drive

Typical adaptive programs

DI1 BMS runcommandDI2 damperend switchNOT DI2AND + TONdelay 60 sRO1 open damperoutput relayRO2 fault to BMSdamper failedStart interlockreleased when provenThe same logic is built with ABB adaptive programming, Siemens free function blocks or a Danfoss Smart Logic Controller
Damper proving start: the drive opens the damper, starts only when the end switch makes, and reports a fault if it does not prove within 60 seconds.
ProgramLogicABBSiemensDanfoss
Damper proving startRun command opens the damper; end switch releases the start; timer raises a fault20.41 start interlock plus AP timer blockFFB AND and PDE timer to the ON/OFF1 sourceSLC event running, action relay on, timer to alarm
Two sensors, control on the worstPick the lower of two pressure readings as PID feedback40.08 feedback function, minimumFFB MIN block to p226420-20 feedback function, minimum
Broken belt or dry pumpPower or torque well below normal at running speed raises an alarm or stopsUser load curve (37) or 32 supervisionLoad monitoring, p218122-2* no-flow, 22-6* broken belt
BMS comms loss fallbackIf the bus goes quiet, run at a safe fixed speed and raise a warning58.14 comm loss actionp2040 telegram monitoring with a fixed setpoint8-03 / 8-04 control word timeout
Fire or smoke modeA fire panel input forces a fixed speed and ignores most faults70 OverrideEssential service mode24-0* fire mode
Duty and standby by run hoursSwap pumps when run hours differ by a set amount76 MultipumpMulti-pump staging25-** cascade controller

Use drive logic for local safety and fallbacks. Keep life-safety interlocks hard-wired and agree with the BMS designer which side owns each function, so the drive and the BMS do not fight.

Commissioning order

  1. NameplateEnter motor voltage, current, kW, frequency and speed, then run motor identification with the load uncoupled if you can.
  2. Macro and I/OPick the closest application macro, then set start source, reference source, relays and analog scaling.
  3. Limits and rampsSet minimum speed for cooling and coil flow, maximum speed for design flow, and ramps the system can take.
  4. PID and sleepScale feedback, set the setpoint, tune gain and integral time, then add sleep and wake-up levels.
  5. SafetyProve start interlocks, external faults, fire mode and the stop mode before handing over.
  6. Network and backupSet the BACnet or Modbus address, check points at the BMS, save parameters and keep a backup file.

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. ABB ACH580 HVAC control program firmware manual
  2. ABB ACH580 flyer: adaptive programming and HVAC assistants
  3. Siemens FAQ: free function blocks on SINAMICS G120
  4. Siemens SINAMICS G120X technical brochure
  5. Danfoss VLT HVAC Drive FC 102 programming guide
  6. Danfoss VACON Programming
  7. Schneider Electric FAQ: ATV Logic function blocks in SoMove
  8. Yaskawa HV600 HVAC drive
  9. Global Market Insights: variable frequency drive market share