Controls and electrical
Variable speed drives (VSD)
Every maker has much the same functions under different names and different parameter numbers. Who builds HVAC drives and what each is known for, the parameters you set on every job with their numbers on ABB, Siemens, Danfoss and Yaskawa, and the built-in logic each one calls something else: adaptive programming, free function blocks, Smart Logic Controller.
Drive makers
| Maker | Founded and base | HVAC drive range | Known for | Built-in logic |
|---|---|---|---|---|
| ABB | ABB formed 1988 (ASEA 1883, Brown Boveri 1891), Switzerland | ACH580, ACH480 | Widely ranked the largest drives maker; HVAC versions with BACnet, fire mode and pump and fan assistants | Adaptive programming |
| Siemens | 1847, Germany | SINAMICS G120P, G120X, G120 | Industry and infrastructure; fits with Desigo BMS and Siemens PLCs | Free function blocks (FFB) wired with BICO; DCC on higher control units |
| Danfoss Drives | Danfoss 1933, Denmark; first mass-produced VLT drive 1968; bought Vacon (Finland) in 2014 | VLT HVAC Drive FC 102, VACON 100 FLOW | Drives-only business; strong in HVAC, water and marine | Smart Logic Controller (SLC); VACON Programming (IEC 61131-3) |
| Schneider Electric | 1836, France | Altivar Process ATV630, ATV650; ATV212 | Building, water and pumping; sold as Square D in North America | ATV Logic function blocks in SoMove |
| Yaskawa | 1915, Japan | HV600 (replaced Z1000) | Largest Japanese drives maker; big in US HVAC; BACnet, Metasys N2 and APOGEE built in | DriveWorksEZ |
| Rockwell Automation (Allen-Bradley) | 1903, USA | PowerFlex 525, 755 | Industrial plants running Logix PLCs | DeviceLogix |
| Mitsubishi Electric | 1921, Japan | FR-F800 | Fans and pumps across Asia | Built-in PLC function (GX Works) |
| Invertek Drives | 1998, UK; now part of Sumitomo Heavy Industries | Optidrive Eco | Compact drives, common inside packaged AHUs and pump sets | OptiTools Studio PLC function blocks |
| Nidec Control Techniques | 1973, UK; Nidec since 2017 | Commander, Unidrive M | Industrial and machine control | Onboard PLC (Machine Control Studio) |
| WEG | 1961, Brazil | CFW500, CFW11 | Motors and drives sold together at good prices | SoftPLC |
| Delta Electronics | 1971, Taiwan | CP2000, C2000 | Low-cost drives with many features | Built-in PLC |
Market lists differ between reports; ABB, Siemens, Danfoss, Schneider and Yaskawa appear at the top of most. In NZ and Australian buildings you mostly meet ABB, Danfoss, Siemens and Schneider, plus whatever drive the AHU or pump maker fitted.
Same setting, different parameter number
| Setting | ABB ACH580 | Siemens G120X / G120P | Danfoss FC 102 | Yaskawa HV600 |
|---|---|---|---|---|
| Motor nameplate | 99.06–99.10 | p0304–p0311 | 1-20 – 1-25 | E1, E2 |
| Motor identification run | 99.13 | p1900 | 1-29 AMA | T1 auto-tuning |
| Application macro | 96.04 | p0015 | Quick menu Q3 | A1-06 |
| Control mode (vector or V/f) | 99.04 | p1300 | 1-01 | A1-02 |
| Start and stop source | 20.01 | p0840 | 5-1* and 8-01 | b1-02 |
| Speed or frequency reference | 22.11 / 28.11 | p1000 / p1070 | 3-15 | b1-01 |
| Minimum and maximum speed | 30.11–30.14 | p1080 / p1082 | 4-11 – 4-14 | d2-01 / d2-02 |
| Acceleration and deceleration | 23.12 / 23.13 or 28.72 / 28.73 | p1120 / p1121 | 3-41 / 3-42 | C1-01 / C1-02 |
| Flying start (catch a spinning fan) | 21.01 | p1200 | 1-73 | b3-01 |
| Fault auto-reset | 31.12–31.15 | p1210 | 14-20 | L5-01 |
| Analog input scaling | 12.17–12.20 | p0756–p0760 | 6-1* | H3-xx |
| Analog output | 13.12 | p0771 | 6-5* | H4-01 |
| Relay outputs | 10.24 / 10.27 / 10.30 | p0730–p0732 | 5-40 | H2-01 |
| Process PID | 40.xx | p2200–p2285 | 20-** | b5-xx |
| Sleep (hibernation) | 40.43 / 40.44 | Hibernation, p2398 | 22-4* | b5-15 |
| Fire mode or override | 70 Override | Essential service mode, p3880 | 24-0* | Fire mode input, H1 |
| Fieldbus protocol | 58.01 | p2030 | 8-30 | H5-xx |
| Actual values (speed, current, kW, DC bus) | 01.xx | r0021–r0039 | 16-** | U1-xx |
| Faults and alarm log | 04.xx | r0945 / r2122 | 15-3* | U2 / U3 |
| Save or factory reset | 96.06 / 96.07 | p0971 / p0970 | 14-22 | A1-03 |
Numbers shift between firmware versions and between the HVAC and industrial variants of the same drive. Use these to find your way in the manual, then confirm against the firmware manual for the exact drive.
ABB parameter groups at a glance
| Parameter group | Group name | What you look at or set |
|---|---|---|
| 01 | Actual values | Speed, frequency, current, kW, torque, DC bus voltage, kWh, PID feedback |
| 03 | Input references | References received from I/O, the fieldbus adapter or embedded fieldbus |
| 04 | Warnings and faults | Active fault, active warnings and the fault log |
| 05 | Diagnostics | On-time, run time, fan run time, inverter temperature |
| 06 | Control and status words | Main control word, main status word, start inhibit reasons |
| 07 | System info | Drive rating, firmware name and version |
| 10–15 | I/O | DI status, relay sources, DIO, AI and AO scaling, extension modules |
| 19–23 | Operation, start and stop, speed reference and ramps | Ext1 and Ext2, run enable, start interlocks, start and stop modes, constant speeds, ramps |
| 28 | Frequency reference chain | The same as group 22 and 23 for scalar (frequency) control |
| 30 | Limits | Minimum and maximum speed and frequency, current and torque limits |
| 31 | Fault functions | External events, fault reset, auto-reset, phase loss, earth fault, stall |
| 32 | Supervision | Three supervision functions that watch any signal against limits and act |
| 40 | Process PID set 1 | Setpoint, feedback, gain, integration time, sleep and wake-up |
| 58 | Embedded fieldbus | BACnet MS/TP or Modbus RTU address, baud rate and comms-loss action |
| 70 | Override | Fire mode speed and source, faults that are ignored |
| 76 | Multipump | Pump staging, alternation and run-time balancing |
| 96 / 99 | System and motor data | Macro, save and restore; motor nameplate, control mode, ID run |
Built-in drive logic
Every maker lets you add a little logic inside the drive so it can run safely without a PLC. Each one has its own name and editor, but they all have the same parts: logic gates, comparators, timers, counters, switches and maths, wired to drive signals, inputs and outputs.
| Maker | Logic tool | How it is programmed |
|---|---|---|
| ABB | Adaptive programming | Graphical blocks in Drive Composer or on the panel; a sequence program with states for step logic |
| Siemens | Free function blocks (FFB), BICO | Blocks are enabled, given a run-time group, then joined by setting one parameter to another’s output (BICO); DCC for larger charts |
| Danfoss | Smart Logic Controller (SLC), group 13 | Up to 20 steps of event then action, with comparators, timers, logic rules and flip-flops |
| Vacon | VACON Programming | IEC 61131-3 languages; needs training and the PC tool |
| Schneider | ATV Logic | Function blocks in SoMove that can be exported and reused |
| Yaskawa | DriveWorksEZ | Drag-and-drop block editor on a PC |
| Rockwell | DeviceLogix | Boolean and function-block logic inside PowerFlex drives |
| Others | Built-in PLC, SoftPLC, OptiTools Studio, onboard PLC | Mitsubishi, Delta, WEG, Invertek and Control Techniques run small PLC programs in the drive |
Typical adaptive programs
| Program | Logic | ABB | Siemens | Danfoss |
|---|---|---|---|---|
| Damper proving start | Run command opens the damper; end switch releases the start; timer raises a fault | 20.41 start interlock plus AP timer block | FFB AND and PDE timer to the ON/OFF1 source | SLC event running, action relay on, timer to alarm |
| Two sensors, control on the worst | Pick the lower of two pressure readings as PID feedback | 40.08 feedback function, minimum | FFB MIN block to p2264 | 20-20 feedback function, minimum |
| Broken belt or dry pump | Power or torque well below normal at running speed raises an alarm or stops | User load curve (37) or 32 supervision | Load monitoring, p2181 | 22-2* no-flow, 22-6* broken belt |
| BMS comms loss fallback | If the bus goes quiet, run at a safe fixed speed and raise a warning | 58.14 comm loss action | p2040 telegram monitoring with a fixed setpoint | 8-03 / 8-04 control word timeout |
| Fire or smoke mode | A fire panel input forces a fixed speed and ignores most faults | 70 Override | Essential service mode | 24-0* fire mode |
| Duty and standby by run hours | Swap pumps when run hours differ by a set amount | 76 Multipump | Multi-pump staging | 25-** cascade controller |
Use drive logic for local safety and fallbacks. Keep life-safety interlocks hard-wired and agree with the BMS designer which side owns each function, so the drive and the BMS do not fight.
Commissioning order
- NameplateEnter motor voltage, current, kW, frequency and speed, then run motor identification with the load uncoupled if you can.
- Macro and I/OPick the closest application macro, then set start source, reference source, relays and analog scaling.
- Limits and rampsSet minimum speed for cooling and coil flow, maximum speed for design flow, and ramps the system can take.
- PID and sleepScale feedback, set the setpoint, tune gain and integral time, then add sleep and wake-up levels.
- SafetyProve start interlocks, external faults, fire mode and the stop mode before handing over.
- Network and backupSet the BACnet or Modbus address, check points at the BMS, save parameters and keep a backup file.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.
- ABB ACH580 HVAC control program firmware manual
- ABB ACH580 flyer: adaptive programming and HVAC assistants
- Siemens FAQ: free function blocks on SINAMICS G120
- Siemens SINAMICS G120X technical brochure
- Danfoss VLT HVAC Drive FC 102 programming guide
- Danfoss VACON Programming
- Schneider Electric FAQ: ATV Logic function blocks in SoMove
- Yaskawa HV600 HVAC drive
- Global Market Insights: variable frequency drive market share