Air conditioning and air distribution

Air conditioning systems

About ten complete systems cover almost every building you will walk into. Each one here comes with its parts list and a diagram: the refrigeration cycle, water-cooled chillers and their cooling tower temperatures, air-cooled chillers, AHUs, fan coils, rooftop units, splits, VRF and hybrid VRF, heat pumps and kitchen pollution control units. Then the formulas, refrigerants and energy numbers that go with them.

1 TR = 3.517 kWOne ton of refrigeration is 12,000 BTU/h
Q = 1.2 × L/s × ΔTSensible heat carried by air, in watts
7 °C / 12 °CTypical chilled water supply and return temperatures

Which system for which building

SystemHow the cooling travelsBest forTrade-offs
Split and ducted DXRefrigerant from one outdoor unit to one indoor unitHouses, shops, small officesSimple and cheap; one zone per system.
VRF / VRVRefrigerant from one outdoor unit to many indoor units, even when air is then ductedMany rooms at different temperatures: offices, hotels, schoolsFlexible zoning and heat recovery; refrigerant charge and leak detection in small rooms need checking (AS/NZS 5149).
Rooftop package (RTU)Refrigerant stays in the rooftop unit; cooling travels as air through ductsOne large space at one temperature: supermarkets, warehouses, hallsEconomical and easy to service; limited zoning.
Water-cooled chiller plantChillers make chilled water for AHUs and FCUs and reject heat to condenser water and cooling towersLarge and complex buildings: hospitals, campuses, high-rise offices, data centresMost efficient at scale; needs plant rooms, towers, water treatment and Legionella management.
Air-cooled chillerPackaged chiller rejects heat straight to outdoor air through fans; chilled water to AHUs and FCUsMid-size offices, schools, hospitals and retrofits without space for towersNo towers or condenser water; uses more energy than water-cooled plant; often reversible as a heat pump.
Hybrid VRFRefrigerant to a hybrid BC controller, then water to fan coilsHotels, aged care, apartments, offices with small roomsKeeps refrigerant out of occupied rooms; fewer suppliers and products.
Air-to-water heat pumpOutdoor heat pump makes heating or chilled water for fan coils, radiators or underfloorHomes, schools, small commercial buildings replacing boilersLow-carbon heating; size emitters for low water temperatures.

The refrigeration cycle

Every air conditioner, chiller and heat pump uses the same vapour compression cycle. The refrigerant boils in the evaporator and absorbs heat, the compressor raises its pressure and temperature, it gives the heat away as it condenses, and the expansion valve drops the pressure again. A heat pump runs the same cycle with a reversing valve so the indoor coil can be either the evaporator or the condenser.

CondenserEvaporatorCompressorExpansion valveheat out to outdoor air or condenser waterheat in from room air or chilled waterhot gas ~70 °Cliquid ~40 °Ccold mix ~5 °Csuction gas ~10 °CHIGH PRESSURELOW PRESSURE
Typical temperatures for a split system cooling a room; exact values depend on the refrigerant and the conditions.

Water-cooled chiller plant with cooling tower

The chiller is the heart of a central plant. Chilled water carries heat from the AHUs and fan coils to the chiller evaporator; the condenser rejects it to condenser water, which the cooling tower cools by evaporating a small part of it into the outdoor air. Water-cooled plant is the most efficient choice for large buildings.

Cooling towerfanoutdoor wet bulb ~24 °CCondenser ~37 °CEvaporator ~4 °CChillerCCW pumpCHW pump29.5 °C35 °C6.7 °C12.2 °CAHUoff coil ~13 °Crooms ~23 °CFan coil unitsexpansion tankcondenser water (to cooling tower)chilled water (to AHUs and FCUs)refrigerant (inside the chiller)tower approach ≈ 5 K above wet bulbboth water loops ≈ 5.5 K range
Typical design temperatures: chilled water 6.7 °C supply and 12.2 °C return; condenser water 29.5 °C to the chiller and 35 °C back to the tower; refrigerant evaporating about 4 °C and condensing about 37 °C.

Components

  • Chillers: centrifugal, screw or scroll compressors, evaporator and condenser shells, expansion device and controls.
  • Cooling towers: open or closed circuit, with fans, fill, drift eliminators, basin, make-up and bleed.
  • Pumps: chilled water (primary and often secondary) and condenser water, duty and standby.
  • Pipework, isolating and balancing valves, strainers, flow switches, air separators and an expansion vessel.
  • Water treatment and dosing, and Legionella control for the tower.
  • Air handling units, fan coils or chilled beams on the load side, and the BMS that stages it all.

Design points

  • Both loops usually run about a 5.5 K range (10 °F).
  • The tower can only cool water towards the outdoor wet bulb; leaving water is typically 3–5 K above it (the approach).
  • Every 1 K warmer chilled water or cooler condenser water saves roughly 2–4% of chiller energy.
  • Towers need registration, a risk management plan and regular testing for Legionella in New Zealand and Australia.

Air-cooled chiller

An air-cooled chiller rejects heat straight to outdoor air through finned coils and fans, so there is no cooling tower, condenser water or tower water treatment. It is simpler and common in mid-size buildings, but uses more energy than water-cooled plant because it condenses at a higher temperature.

Air-cooled chillerevaporatoroutdoor air 35 °Cwarm air out ~45 °Crefrigerant condensing ~48 °Cbuffer tankpump7 °C12 °CAHUFCUs
Air-cooled chiller with a buffer tank and a single chilled water loop to the AHU and fan coils.

Components

  • Packaged chiller on the roof or ground: compressors, evaporator, air-cooled condenser coils and fans, controls.
  • Chilled water pumps, often built in; a buffer tank for minimum system volume.
  • Glycol where pipes are exposed to frost.

What to check

  • Clear space around the coils so hot discharge air is not drawn back in.
  • Noise at neighbours, and weight and seismic restraint on the roof.
  • Many air-cooled chillers are also heat pumps (reversible), giving heating water in winter.

Air handling unit (AHU)

The AHU conditions and moves the air. On a roof or in a plant room, it mixes outdoor and return air, filters it, cools or heats it with coils, and pushes it through ducts to the rooms. A dedicated outdoor air unit (DOAS or “fresh air unit”) treats only outdoor air for other terminal units.

OAdampermixingboxprefilterheatrecoverybagfiltercoolingcoilheatingcoilsupply fanhumidifiersilenceroutdoor airsupply airRFreturn fan, EA damperreturn airexhaustdrain pan under the coils · access doors on every section · VSD on each fan
Sections of a typical AHU in airflow order; not every unit has every section.

Components

  • Casing with access doors, insulated double-skin panels and a drain pan.
  • Outdoor, return and exhaust dampers with actuators; a mixing box.
  • Pre-filters and bag or high-efficiency filters, with differential pressure gauges.
  • Heat recovery: a plate exchanger, thermal wheel or run-around coil.
  • Cooling coil (chilled water or DX) and heating coil (hot water, electric or gas).
  • Supply and return fans, usually EC fans or plug fans on VSDs; humidifier and silencers where needed.

Typical numbers

  • Off-coil air about 12–14 °C for comfort cooling; rooms 22–24 °C.
  • Coil face velocity about 2.5 m/s to avoid carrying condensate off the coil.
  • Fresh air to NZS 4303 or AS 1668.2, often controlled on CO₂.

Heat recovery units (HRU)

Every litre of outdoor air you bring in has to be heated or cooled to room condition, and every litre you throw out takes that energy with it. A heat recovery unit puts the two airstreams next to each other and moves the heat across. In a house it is the whole ventilation system; in a commercial building it is a section inside the AHU.

outdoor air5 °Csupply air18 °Creturn air21 °Cexhaust air8 °Csummer bypass dampercounter-flowplate corefilterfilterextract fansupply fancondensateBlue is outdoor air on its way to the rooms; orange is air on its way out. In a plate core the two never mix.
A counter-flow plate HRU. Supply and extract pass either side of the plates, so heat crosses but air does not.

What decides the type

  • Can the two airstreams touch? A hospital isolation room, a lab fume exhaust or a kitchen extract rules out wheels and leaky plate cores.
  • Are they in the same place? If supply and extract plant are at opposite ends of the building, a run-around loop is the only one that works.
  • Do you want the moisture? Recovering humidity helps in a dry winter and in a humid summer, and a wheel is the usual way to get it.
  • How much pressure can the fan spare? Higher efficiency almost always means more pressure drop and a bigger fan.

Frost, and why units fail in winter

  • Warm, moist extract air gives up its moisture in the core. Below about −3 °C outside that condensate freezes and blocks the extract side.
  • Defence one: modulate a bypass damper so less cold air hits the core. Cheapest, costs you recovery.
  • Defence two: an electric or hydronic preheater on the outdoor air. Reliable, and it costs the energy you were trying to save.
  • Defence three: slow the supply fan so the extract side stays warmer. Free, but the building goes slightly negative and gets draughty.
  • A core needs a condensate drain with a trap, and the trap needs water in it. A dry trap in a negative-pressure unit pulls air and smells.

Controls that matter

  • Summer bypass: when outside is cooler than return air and the building wants cooling, send supply air around the core instead of through it.
  • Filters both sides. The extract filter is the one people forget, and it is the one that fouls the core.
  • Measure efficiency from four temperatures, not from the brochure: supply, outdoor, return and exhaust.
  • Balance supply against extract. An unbalanced unit reports a flattering efficiency and pressurises or depressurises the building.
TypeHow it worksSensible efficiencyMoistureWhere it suits
Counter-flow plateThe two airstreams run in opposite directions either side of thin plates85–93%Sensible only, unless the plates are a membraneHouses and small commercial: the usual choice for residential MVHR
Cross-flow plateThe airstreams cross at right angles50–70%Sensible onlyCompact AHU sections where depth is tight
Thermal wheelA slowly turning matrix picks up heat from one stream and gives it to the other70–85%An enthalpy or desiccant wheel moves moisture tooLarge AHUs where supply and extract sit side by side
Run-around coil loopA coil in each airstream with a pumped water or glycol loop between them45–65%Sensible onlyWhen the two airstreams are nowhere near each other, or must never mix
Heat pipeSealed refrigerant pipes move heat from the warm side to the cool side with no moving parts45–65%Sensible onlyWhere reliability matters more than peak efficiency

Sensible efficiency from a plate core is measured dry. Once the extract side starts condensing, the real heat transfer goes up because latent heat is released in the core, while the figure on the data sheet stays where it was. Judge an installed unit on the four temperatures, not on the label.

Fan coil units (FCU)

A fan coil is a small air handler for one room or zone: a fan, a coil and a filter, usually hidden in the ceiling. Two-pipe units get chilled or hot water depending on the season; four-pipe units have separate cooling and heating coils so neighbouring rooms can heat and cool at the same time.

filterfancoil(s)return grillesupply diffusersdrain pan, condensate pumpCHWHWroomcontrollerceiling voidroom below2-way or 3-way valve on each coil
Ceiling fan coil with return grille, filter, fan, coils, drain pan, valves and a room controller.

Components

  • EC or three-speed fan, cooling coil and heating coil (or one coil for two-pipe), filter.
  • Drain pan and condensate pump where gravity drainage is not possible.
  • Two-way or three-way control valves with actuators, isolating valves and flexible hoses.
  • Room controller or BMS connection; fresh air ducted in from a DOAS or AHU.

Where it fits

  • Offices, hotels, hospitals and apartments on chilled and hot water plant.
  • Water-based FCUs keep refrigerant out of occupied rooms.

Packaged rooftop unit (RTU)

A rooftop unit puts the whole refrigeration system, the supply fan and the filters in one weatherproof box on a roof curb, with supply and return ducts straight down into the building. Heating comes from a heat pump reversing valve, gas burners or electric heaters.

economiserdampersfiltersevaporatorcoilsupply fancompressorscondenser fans and coilsOA hoodsupplyreturnroof curbone package: refrigerant never leaves the unit
Rooftop unit: economiser, filters, evaporator, supply fan, compressors and condenser in one package.

Components

  • Compressors (often two for staging), evaporator and condenser coils, condenser fans.
  • Supply fan (and sometimes a return or relief fan), filters, economiser dampers.
  • Heating: heat pump, gas heat exchanger or electric heater; controls and BMS interface.
  • Roof curb, vibration isolation and seismic restraint.

Where it fits

  • Supermarkets, warehouses, retail, halls and single-storey buildings with one large space.
  • Quick to install and service; less efficient and less zoning than central plant.

Split and ducted DX

Components

  • Outdoor unit with compressor, condenser coil and fan.
  • Indoor unit: wall, cassette, floor or ducted, with evaporator coil, fan and filter.
  • Insulated refrigerant pair, condensate drain, power and communication cable, controller.
  • Ducted units add a return plenum, filter grille, ducts, zone dampers and diffusers.

Where it fits

  • Houses, apartments, shops, small offices, server rooms.
  • One outdoor unit per indoor unit (multi-splits connect a few); pipe length and height limits apply.

VRF / VRV

Variable refrigerant flow systems connect one outdoor unit, or a group of them, to many indoor units through a single refrigerant pipe network. Inverter compressors vary the refrigerant flow to match the load. Heat pump VRF either heats or cools at one time; heat recovery VRF can heat some rooms while cooling others, moving heat between them through a BC controller or a three-pipe system.

Outdoor unit(s)inverter compressorsBC controller(heat recovery only)ceiling cassetteducted unitwall unitfloor unitcentralcontrollerliquid + gas pipesrefnet joints orbranch headerscontrol wiring
VRF: outdoor units, refrigerant pipes split by refnet joints (or a BC controller for heat recovery) to many indoor unit types.

Components

  • Outdoor units with inverter compressors; modules combine for larger capacity.
  • Refrigerant pipework with branch joints or headers; BC controller or mode change boxes for heat recovery.
  • Indoor units: cassettes, ducted, wall, floor and fresh air units.
  • Local and central controllers, BMS gateway (BACnet or Modbus), refrigerant leak detection.

What to check

  • Total refrigerant charge against the smallest room it can leak into (AS/NZS 5149); add leak detection or ventilation if needed.
  • Pipe length, height difference and connection ratio within the maker’s limits.
  • Brazing with nitrogen, pressure testing and accurate additional charge.

Hybrid VRF (HVRF)

Mitsubishi Electric’s Hybrid VRF runs refrigerant only between the outdoor unit and a Hybrid BC controller. Plate heat exchangers and inverter pumps in the controller pass the energy to water, and water, not refrigerant, goes to the indoor fan coils. It still heats and cools at the same time on two pipes, cuts the total refrigerant charge, and keeps refrigerant out of occupied rooms.

Outdoor unitHybrid BC controllerplate heat exchangers + pumps2 refrigerant pipesfan coil, room 1fan coil, room 2fan coil, room 3occupied rooms: water only, no refrigerantplant area: refrigerant
Hybrid VRF: two refrigerant pipes to the Hybrid BC controller, then water circuits to fan coils in each room.

Components

  • VRF outdoor unit (air-source or water-source).
  • Main Hybrid BC controller, plus sub controllers for more zones.
  • Water pipework (two pipes to each unit) and water-coil indoor units.
  • Controls as for VRF, with water treatment and frost protection for the water circuit.

Why use it

  • Hotels, aged care, apartments and offices where refrigerant limits in small rooms are a problem.
  • Easier compliance with refrigerant safety standards and lower leak risk.
  • Check model, refrigerant (R410A or R32) and which versions can heat and cool at the same time.

Heat pumps

A heat pump moves heat instead of making it, delivering about 3–4 kW of heat for every kW of electricity. The source can be outdoor air, water or the ground, and the output can be air or water.

Outdoor heat pumpbuffer tankpump3-way valvefan coilsradiatorsunderfloorhot water cylinderheating 35–55 °Ccooling 7–18 °C
Air-to-water heat pump with a buffer tank serving fan coils, radiators or underfloor heating, and a hot water cylinder through a three-way valve.
TypeSource and outputTypical use
Air-to-airOutdoor air to room air (splits, ducted, VRF)Most homes and offices
Air-to-waterOutdoor air to heating or chilled waterUnderfloor heating, radiators, fan coils, reversible chillers
Water-source loopUnits share a water loop held at about 18–32 °C by a tower and boilerMulti-storey buildings that heat and cool at once
Ground-sourceGround loops or bores to waterHigh efficiency where land or bores allow
Hot water heat pumpAir or waste heat to domestic hot water (CO₂ or two-stage)Hotels, hospitals, aged care, swimming pools

Kitchen exhaust pollution control unit (PCU)

Where kitchen exhaust cannot be discharged high above the roof, or neighbours are close, a pollution control unit cleans the exhaust after the hood. It is a passive filter train installed upstream of the exhaust fan.

hood withgrease bafflespre-filterelectrostaticprecipitatorhigh-efficiencyor HEPAcarbon odourmoduleaccessexhaust fanpollution control unit (PCU): grease, smoke and odour removed before discharge
A typical PCU filter train between the kitchen hood and the exhaust fan.

Components

  • Washable steel pre-filter for grease.
  • Electrostatic precipitator (ESP) cells, often self-cleaning, for smoke.
  • High-efficiency (MERV 14–15) or HEPA filters for fine particles.
  • Activated carbon or carbon and permanganate module last, for odour.
  • Stainless steel housing, access doors, pressure gauges and fire suppression where required.

What to check

  • Filter pressure losses add up; select the exhaust fan for dirty filters.
  • Filter change and cleaning schedule, and access for it.
  • Council and fire requirements for kitchen exhaust; the PCU does not replace the hood’s fire protection.

Other systems you will meet

SystemHow it worksMain componentsWhere it fits
Evaporative coolingWater evaporating from wet pads cools the air (direct), or cools a separate airstream through a heat exchanger (indirect)Pads, pump, float valve, bleed, fan, ductsDry climates, warehouses, factories, many Australian homes
Chilled beams and radiant panelsChilled water at about 14–17 °C, above the dew point, cools rooms by convection or radiationActive or passive beams, radiant ceilings, DOAS for fresh air and dehumidificationOffices and labs with high sensible loads and good humidity control
DOAS and heat recovery ventilationA dedicated unit treats 100% outdoor air and recovers heat from the exhaustPlate exchanger or wheel, filters, coils, fansSchools, apartments, Passive House, with FCUs or VRF
Boilers and hydronic heatingGas, electric or biomass boilers heat water for coils, radiators or underfloorBoilers, pumps, flue, expansion and pressurisation, controlsSchools, hospitals, older buildings; heat pumps are replacing many
Close control (CRAC and CRAH)Precision units hold tight temperature and humidity for IT and labsDX or chilled water coils, EC fans, humidifiers, controlsData centres, server and communications rooms
Absorption chillersHeat (waste heat, steam or gas) drives the cycle instead of a compressorGenerator, absorber, condenser, evaporator, lithium bromide solutionSites with spare heat, such as cogeneration plants
Thermal storageChill water or make ice off-peak and use it at peak timesIce tanks or stratified water tanks, glycol chillers, heat exchangersLarge sites with time-of-use tariffs or limited power supply

Formulas you use every day

QuantityFormulaUnits used
Sensible heat in airQ = 1.2 × airflow × ΔTW, L/s, K
Latent heat in airQ = 3.0 × airflow × ΔmoistureW, L/s, g/kg
Heat in waterQ = flow × 4.18 × ΔTkW, L/s, K
Airflow from air changesL/s = volume × ACH ÷ 3.6L/s, m³, per hour
Pump powerP = ρ × g × H × Q ÷ efficiencyW, kg/m³, m/s², m, m³/s
Thermal transmittanceU = 1 ÷ RW/m²K; lower U is better
EfficiencyCOP or EER = cooling or heating output ÷ power inputkW ÷ kW

Total cooling load = internal gains (people, lights, equipment) + solar and fabric gains + outdoor air load. Equipment heat is usually far below nameplate power: a printer rated 1344 W averages about 130 W.

Refrigerants

RefrigerantGlobal warming potential (GWP)Where you see itNotes
R221810Old splits and chillersOzone-depleting HCFC; no longer imported for new equipment.
R410A2088Splits, VRF and packages from the 2000s and 2010sBeing phased down; higher pressure than R22.
R32675Most new splits and many VRF systemsMildly flammable (A2L); charge limits in small rooms.
R134a1430Screw and centrifugal chillers, heat pump boostersLow pressure; being replaced by lower-GWP HFOs.
R744 (CO₂)1Supermarket refrigeration, hot water heat pumpsVery high pressure (transcritical systems run above about 73 bar).
R290 (propane)3Small heat pumps and display cabinetsHighly flammable (A3); strict charge limits.

GWP values are the IPCC AR4 figures used for HFC phase-down accounting. Only certified people may handle refrigerants in New Zealand and Australia.

Where the energy goes

Plant selection

  • Air conditioning is often 40% or more of a commercial building’s electricity.
  • Choose chillers and heat pumps on part-load efficiency (IPLV), not only full-load EER.
  • Size to the calculated load; oversized plant cycles and wastes energy.

Operation

  • Variable-speed pumps and fans with sensible reset of supply temperature and duct pressure.
  • Economy cycle (free cooling with outdoor air) when outdoor conditions allow.
  • Time schedules, after-hours buttons and CO₂ control of outdoor air.

Maintenance

  • Clean coils and filters; dirty coils raise condensing pressure and power.
  • Treat cooling tower water and keep records under AS/NZS 3666.
  • Trend energy and plant data in the BMS and act on drift.

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. ASHRAE Handbook – Fundamentals (psychrometrics and load calculation)
  2. AS/NZS 5149 Refrigerating systems and heat pumps – safety and environmental requirements
  3. AS/NZS 3666 Air-handling and water systems of buildings – microbial control
  4. Ministry for the Environment: HFC phase-down in New Zealand
  5. IPCC Fourth Assessment Report (AR4) global warming potentials