Online training
HydroPlan training
Water, waste and stormwater all run off the same floor plan and all have their own rules. HydroPlan keeps the three layers together and checks each one as you draw.
AS/NZS 3500The plumbing and drainage standard the sizing follows
G12 / G13NZ Building Code clauses for water supplies and foul water
3 m/sVelocity worth staying under in copper and PEX, or you hear the pipe
The three layers
Cold and hot water
- Fixtures carry loading units; the tool adds them up along each run and sizes from there.
- Hot water adds dead-leg length and the tempering valve where one is required.
Foul drainage
- Fixture units set the pipe size, and every branch needs a fall and a vent path.
- Traps, inspection openings and the connection to the public sewer are placed as you go.
Stormwater
- Roof area and the local rainfall intensity set gutter, downpipe and drain sizes.
- Detention or soakage gets added where the council asks for it.
Step by step
- Draw the planTrace the building and mark wet areas. Everything else hangs off the fixture positions.
- Place fixturesDrop in basins, showers, WCs, sinks and the laundry. Each one brings its own loading and fixture units.
- Run the water layerConnect from the point of supply through to each fixture; the tool sizes each section.
- Check pressure and velocityLook at the worst fixture. Pressure at the outlet and velocity in the pipe both have to pass.
- Run the drainage layerSet falls, add vents and check the stack. Branch length and fall limits are checked for you.
- Run the stormwater layerEnter the roof areas and rainfall intensity, then size gutters, downpipes and the connection.
- Export the reportThe schedule lists every pipe size with the clause it was sized against.
What the tool checks for you
| Check | What it means | What to do when it flags |
|---|---|---|
| Outlet pressure | The worst fixture does not get enough pressure | Increase the main size, shorten the run, or add a pump |
| Pipe velocity | Water is moving fast enough to be heard or to erode copper | Go up one size on that section |
| Drain fall | A branch is flatter or steeper than the standard allows | Adjust the invert levels, or shorten the branch |
| Reducing in the direction of flow | A drain gets smaller downstream, which is not allowed | Keep the downstream size at or above the upstream size |
| Hot water temperature | A sanitary fixture is served without tempering | Add a tempering valve to that branch |