Auxuro

Water, fire and power

Hot water and hydronic plant

The heat pump or chiller is the machine everyone looks at. The rest of the plant room decides whether it works: storage and buffer tanks, expansion and make-up, dosing and filtration, pump sets, and heat recovery off the refrigeration plant.

2205Duplex stainless for hot water tanks: about twice the strength of 316 with better pitting resistance
AS 1210Pressure vessel standard that commercial storage and buffer tanks are usually quoted to
Duty / standbyTwo pumps or a twin-head pump so one failure does not stop the system

Storage and buffer tanks

Why a buffer tank

  • Heat pumps and chillers need a minimum water volume so they do not short-cycle at low load.
  • A buffer also separates the plant flow from the building flow and evens out temperature swings.
  • Sizes run from about 1000 L for a single store to 10,000 L or more for hospitals.

What to specify

  • Inner vessel: 2205 duplex or 304/316 stainless for potable hot water; carbon steel is common for closed heating loops.
  • Insulation (often 50 mm polyurethane) with a thin stainless or Colorbond outer jacket.
  • Connections as AS 2129 Table E flanges or threaded sockets, plus a drain, air vent, sensor pockets and a sacrificial anode where needed.
  • Design and test pressure to AS 1210, a stainless drip tray where a leak would cause damage, and seismic hold-down feet designed to AS 1170.4 or NZS 4219.

Pressurisation, make-up and treatment

Expansion and make-up

  • Closed loops need an expansion vessel sized for the system volume and temperature range.
  • An automatic make-up unit tops up from mains through a break tank or backflow device and keeps the fill pressure.
  • Air separators and automatic air vents at high points; dirt separators or strainers before pumps and plate heat exchangers.

Water treatment

  • A dosing pot on a bypass lets you add inhibitor to closed loops; test and record the water each year.
  • Copper–silver ionisation is one option for controlling Legionella in hot water systems.
  • Incoming water metering and self-cleaning filters protect plant on large sites.

Pumps

Selection

  • Flow from the heat load: L/s = kW ÷ (4.18 × ΔT).
  • Head from the index circuit: pipe friction, fittings, coils, heat exchangers and control valves.
  • Variable-speed pumps with pressure control save energy where flow varies.

Packaging

  • Duty/standby pairs, or twin-head pumps, with automatic changeover on failure.
  • Skid-mounted pump sets with the expansion vessel, valves and controls pre-piped save site time.
  • Stainless pumps for potable hot water; cast iron for closed heating and chilled water.

Heat recovery and hot water plant

Refrigeration heat recovery

  • Supermarket refrigeration rejects heat all day; a heat exchanger on the discharge gas can preheat hot water.
  • CO₂ systems are especially good for this because their discharge temperatures are high.
  • Store the recovered heat in a buffer and top up with a heat pump or water heater to 60 °C.

Commercial water heating

  • Choose between storage, heat exchanger (calorifier) and instantaneous systems on the peak demand profile.
  • Solar evacuated tube arrays and heat pumps cut running cost; size storage to bridge the peaks.
  • Keep circulation loops at 60 °C and balance them so every branch stays hot.

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. AS 1210 Pressure vessels
  2. AS/NZS 3500.4 Heated water services
  3. AS/NZS 3666 Air-handling and water systems of buildings – microbial control
  4. ASHRAE Handbook – HVAC Systems and Equipment (hydronic heating and cooling)