Water, fire and power
Hot water and hydronic plant
The heat pump or chiller is the machine everyone looks at. The rest of the plant room decides whether it works: storage and buffer tanks, expansion and make-up, dosing and filtration, pump sets, and heat recovery off the refrigeration plant.
2205Duplex stainless for hot water tanks: about twice the strength of 316 with better pitting resistance
AS 1210Pressure vessel standard that commercial storage and buffer tanks are usually quoted to
Duty / standbyTwo pumps or a twin-head pump so one failure does not stop the system
Storage and buffer tanks
Why a buffer tank
- Heat pumps and chillers need a minimum water volume so they do not short-cycle at low load.
- A buffer also separates the plant flow from the building flow and evens out temperature swings.
- Sizes run from about 1000 L for a single store to 10,000 L or more for hospitals.
What to specify
- Inner vessel: 2205 duplex or 304/316 stainless for potable hot water; carbon steel is common for closed heating loops.
- Insulation (often 50 mm polyurethane) with a thin stainless or Colorbond outer jacket.
- Connections as AS 2129 Table E flanges or threaded sockets, plus a drain, air vent, sensor pockets and a sacrificial anode where needed.
- Design and test pressure to AS 1210, a stainless drip tray where a leak would cause damage, and seismic hold-down feet designed to AS 1170.4 or NZS 4219.
Pressurisation, make-up and treatment
Expansion and make-up
- Closed loops need an expansion vessel sized for the system volume and temperature range.
- An automatic make-up unit tops up from mains through a break tank or backflow device and keeps the fill pressure.
- Air separators and automatic air vents at high points; dirt separators or strainers before pumps and plate heat exchangers.
Water treatment
- A dosing pot on a bypass lets you add inhibitor to closed loops; test and record the water each year.
- Copper–silver ionisation is one option for controlling Legionella in hot water systems.
- Incoming water metering and self-cleaning filters protect plant on large sites.
Pumps
Selection
- Flow from the heat load: L/s = kW ÷ (4.18 × ΔT).
- Head from the index circuit: pipe friction, fittings, coils, heat exchangers and control valves.
- Variable-speed pumps with pressure control save energy where flow varies.
Packaging
- Duty/standby pairs, or twin-head pumps, with automatic changeover on failure.
- Skid-mounted pump sets with the expansion vessel, valves and controls pre-piped save site time.
- Stainless pumps for potable hot water; cast iron for closed heating and chilled water.
Heat recovery and hot water plant
Refrigeration heat recovery
- Supermarket refrigeration rejects heat all day; a heat exchanger on the discharge gas can preheat hot water.
- CO₂ systems are especially good for this because their discharge temperatures are high.
- Store the recovered heat in a buffer and top up with a heat pump or water heater to 60 °C.
Commercial water heating
- Choose between storage, heat exchanger (calorifier) and instantaneous systems on the peak demand profile.
- Solar evacuated tube arrays and heat pumps cut running cost; size storage to bridge the peaks.
- Keep circulation loops at 60 °C and balance them so every branch stays hot.