Air conditioning and air distribution
Car park ventilation
Enclosed and underground car parks need ventilation to dilute and clear exhaust gases such as carbon monoxide (CO). Impulse and induction fans do this without bulky overhead ductwork; the controls ramp them on measured CO and change mode when the fire alarm operates.
No ductsImpulse fans push air along the car park towards the exhaust point instead of collecting it through ductwork
CO controlSensors across each zone ramp the fans from a minimum speed up to full speed as CO rises
Fire modeThe fire alarm overrides CO control; what the fans do then is set by the fire engineer
Natural or mechanical
When natural ventilation works
- Building Code clause G4 points car parks to AS 1668.4 for natural ventilation and AS 1668.2 for mechanical ventilation.
- Natural ventilation needs large permanent openings, spread so air can cross the whole floor.
- Where the openings cannot be achieved, the car park must be mechanically ventilated.
- Impulse fans are a mechanical system; they do not turn a car park into a naturally ventilated one.
Ducted or impulse fan systems
- Ducted: exhaust grilles near floor level and ceiling, collected by ducts to central fans.
- Impulse fan system: supply and exhaust fans at the ends, with impulse fans in between moving air in a controlled direction.
- Impulse fans save ceiling height and duct cost, and suit low headroom.
- Airflow paths are usually checked with CFD for large or irregular car parks.
Impulse and induction fans
How they work
- Impulse fans throw a high-velocity jet that drags surrounding air with it.
- Induction fans entrain more surrounding air for a wider, lower-velocity throw, in a slimmer body.
- Many use single-phase EC motors with built-in controllers and a fieldbus connection.
- Some carry CO sensors and optional smoke detectors on the fan itself.
Layout
- Place fans in a line along the airflow path, spaced by their throw at the design velocity.
- Avoid blowing into beams, ramps and parked vehicles close in front of the fan.
- Check clear height to the underside of the fan for vehicles and signs.
Controls
CO demand control
- A controller reads CO sensors in each zone and runs every zone on its highest reading.
- Below the start level the fans idle at minimum speed or stop; above the full-speed level they run at 100%.
- Between the two the speed ramps in proportion.
- A sensor fault should drive its zone to a safe fixed speed, not to zero.
Sensor signals
- Use 4–20 mA where you can: a reading below about 3.5 mA shows a broken wire.
- With 0–20 mA or 0–10 V a broken wire reads as clean air, so the fans slow down.
- Mount sensors at breathing height away from direct exhaust plumes; follow the sensor maker’s spacing.
Fire and smoke mode
- A fire alarm input overrides CO control.
- In many designs impulse fans stop so smoke is not spread while people escape, and supply and exhaust go to full speed.
- Smoke clearance designs run selected impulse fans after a delay; the fire engineer sets the sequence.
- Test the fire mode from the fire panel at commissioning, not just from the controller.
Fault-finding a fan that will not start
- CO levelIs the CO reading below the start level? Then the fan is meant to be idle.
- Fire inputIs a fire or smoke input active, or wired the wrong way (normally open versus normally closed)?
- ModeIs the fan or zone set to Off or Auto rather than On?
- CommunicationIs the fan online? Check the daisy-chain wiring, termination resistors at both ends, and duplicate addresses.
- Supply powerDoes the fan have supply voltage, and has its own protection tripped?
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.