Controls and electrical
Building management systems (BMS)
Controls is the part of HVAC most people move into sideways, usually without training. Start here: what a BMS does, the three levels it is built in, points and points lists, BACnet and the other protocols, the sequences that run most plant, the Siemens range and what each part is for, and how a BMS job gets priced.
What a BMS does
Control
- Starts, stops and modulates plant: AHUs, fans, pumps, chillers, boilers, heat pumps, VAV boxes and fan coils.
- Runs control loops (PID) to hold temperature, pressure, humidity and CO₂ at set points.
- Time schedules, holidays, after-hours buttons and optimum start.
Monitor
- Alarms for faults, high and low values and communication loss, sent to operators by screen, email or SMS.
- Trend logs of every important value for fault-finding and tuning.
- Graphics showing each plant item live.
Integrate and save energy
- Reads meters, chillers, VRF, lighting and lifts over BACnet, Modbus, M-Bus or KNX.
- Energy reports and fault detection and diagnostics (FDD) find waste.
- Interfaces with fire (shutdown, smoke control) and security, usually as monitored signals rather than control.
Architecture
| System level | What sits there | Typical network |
|---|---|---|
| Management | Head-end server and workstations, graphics, alarms, trends, reports, cloud connection | Ethernet, BACnet/IP, IT network |
| Automation | Programmable controllers for plant, routers, integration gateways | BACnet/IP between controllers |
| Field | Sensors, valves, damper actuators, drives, room controllers, meters | Hard-wired I/O, BACnet MS/TP, Modbus RTU, KNX, M-Bus |
Points and points lists
| Point type | Signal | Examples |
|---|---|---|
| DI (digital input) | Volt-free contact, open or closed | Fan status, fault, filter switch, fire alarm, flow switch |
| DO (digital output) | Relay contact | Fan or pump enable, valve open/close, alarm lamp |
| AI (analogue input) | 0–10 V, 4–20 mA, or resistance (Pt1000, NTC) | Temperatures, humidity, CO₂, duct and water pressure |
| AO (analogue output) | 0–10 V or 4–20 mA | Valve position, damper position, VSD speed |
| Software and integration points | Values inside the controller or read over a network | Set points, schedules, occupancy, chiller and meter data over BACnet or Modbus |
Count hardware points by type to size controllers and I/O modules; leave about 10–20% spare. Integration points are priced on engineering time, not hardware.
Worked example: an AHU points list
| Tag | Device | Points | Purpose |
|---|---|---|---|
| RA TS | Return air temperature sensor | AI | Space temperature and economy cycle |
| RA HS | Return air humidity sensor | AI | Space humidity and enthalpy economy cycle |
| VS | Return air velocity or airflow station | AI | Return airflow, used to track the supply fan |
| Spill damper | Spill air damper actuator (M) | AO + AI | Command and position feedback; opens with the outdoor air damper |
| RA damper | Return air damper actuator (M) | AO + AI | Command and feedback; closes as outdoor air opens |
| OA TS | Outdoor air temperature sensor | AI | Economy cycle and reset schedules |
| OA HS | Outdoor air humidity sensor | AI | Enthalpy economy cycle |
| Max OA damper | Economy outdoor air damper actuator (M) | AO + AI | Free cooling with outdoor air |
| Min OA damper | Minimum outdoor air damper actuator (M) | AO + AI | Holds the minimum fresh air rate |
| DP 1 | Filter 1 differential pressure sensor | AI | Dirty filter alarm |
| DP 2 | Filter 2 differential pressure sensor | AI | Dirty filter alarm |
| UV C | UV filter lamp contactor | DI | UV lamp running status |
| CU C | Outdoor condensing unit controller | DO + DI + HLI | Enable, fault and data (capacity, temperatures, alarms) over Modbus or BACnet |
| SA TS | Supply air temperature sensor | AI | Main control variable for cooling |
| SA HS | Supply air humidity sensor | AI | Dehumidification control |
| SMK | Duct smoke detector | DI | Shuts the AHU down on smoke |
| PS | Supply duct static pressure sensor | AI | Supply fan speed control |
| Each VSD fan | Return fan and each supply fan | DO + AO + 2 DI + HLI | Run enable, speed, run status, fault; kW, kWh and fault codes over the network |
| Total without fans | AI 14, AO 4, DI 3, DO 1, HLI 1 | 23 points | Add 1 DO, 1 AO, 2 DI and 1 HLI for each VSD fan |
M is the damper actuator, C a contactor or controller, TS temperature, HS humidity, VS velocity, DP differential pressure, PS static pressure, SMK smoke. Damper AI points are position feedback; keep the smoke shutdown hard-wired as well.
AHU points by type
A typical single-zone or multi-zone AHU, counted by point type. The numbers vary with the design; use them to check a points schedule or to size a controller.
| Type | Full name | Typical count | Examples and purpose |
|---|---|---|---|
| AO | Analogue output: valves, dampers and speed | 3–4 | Outdoor air damper position 0–100%; return, mixing or bypass damper; spill or relief damper; chilled and heating water valves (often PICVs); VSD speed reference. |
| AI | Analogue input: sensors and feedback | 8–12 or more | Temperature (TS) of outdoor, return, mixed and supply air; humidity (HS) of outdoor, return and supply air; filter differential pressure (DP) across the G4 pre-filter and F7 filter; supply static pressure or airflow (PS, VS); damper and valve position feedback. |
| DI | Digital input: status and alarms | several | Supply duct smoke detector (SMK, shuts the unit down); fan run status and trip; UV lamp status or fault; filter switch; fire alarm shutdown; local hand/off/auto. |
| DO | Digital output: start and stop | 1–2 | Supply and return fan start/stop; UV lamp on/off; humidifier enable. |
| HLI | High-level interface over a network | 1 or more | EC fans, VSDs or the AHU’s own packaged controller over Modbus RTU or BACnet/IP: energy, power, current, detailed fault codes and run hours. |
Filter grades G4 and F7 come from the older EN 779 standard; new specifications use ISO 16890 classes such as ePM10 and ePM1. Keep safety functions (smoke shutdown, frost protection) hard-wired even when data comes over HLI.
Points and interfaces for each plant item
Most client BMS standards split each plant item into hard-wired points for control and safety, and a high-level interface (HLI) for the extra data the equipment already has. The table is a typical arrangement; follow the project specification and the equipment maker’s points map.
| Equipment | Connection | Protocol | BMS interface | Hard-wired points | HLI and network points |
|---|---|---|---|---|---|
| AHU | Hard-wired plus bus | BACnet/IP or Modbus RTU | HVAC controller | See the AHU table above | Fan energy and faults, packaged controller data |
| Terminal units (VAV, FCU, chilled beams) | Ethernet, MS/TP or KNX | BACnet/IP, BACnet MS/TP or KNX | Terminal unit controller | Valve (2-way or 3-way, often PICV) AO; fan speed AO or DO; damper AO; supply air temperature AI | Room temperature, humidity and CO₂ from room sensors; airflow, occupancy, set points |
| Chillers | Hard-wired plus bus | BACnet/IP or Modbus | HVAC controller and BACnet | Enable DO; run and common fault DI; chilled water set point AO; flow switch DI | Entering and leaving water temperatures, compressor status and load, refrigerant pressures, refrigerant leak alarm, power and kWh, fault codes |
| Cooling towers | Hard-wired plus VSD bus | Modbus RTU | HVAC controller | Fan start DO, speed AO, run and trip DI; basin high and low level DI; leaving water temperature AI; make-up and bleed valves | VSD energy and faults, conductivity from the water treatment controller |
| Large heat pumps | Hard-wired plus bus | BACnet/IP or Modbus | HVAC controller and BACnet | Enable DO; mode DO; run and fault DI; flow and return temperature AI | COP, power, refrigerant pressures, defrost status, fault codes |
| Boilers | Hard-wired plus bus | Modbus or BACnet | HVAC controller | Enable DO; flow temperature set point AO; run, lockout and fault DI | Flow and return temperatures, firing rate, gas use, fault history |
| Pumps and fans on VSDs | Hard-wired for control, bus for data | Modbus RTU | HVAC controller | Start DO; speed AO; run and trip DI; differential pressure or flow AI | Frequency, current, power, kWh, run hours, fault codes |
| Direct-on-line fans and pumps | Hard-wired | None | HVAC controller | Start DO; run status and trip DI | None |
| Duct heaters | Hard-wired plus HLI | Modbus or BACnet | HVAC controller | Enable DO; output AO; airflow proving and over-temperature cut-out hard-wired | Power, current, element temperature and diagnostics |
| VRF and split systems | Gateway | BACnet/IP or Modbus gateway | Maker’s gateway | Fire shutdown DI to the outdoor unit or controller where required | On/off, mode, set point, room temperature, fault codes for each indoor unit |
| Room sensors | KNX, MS/TP or Modbus | KNX, BACnet MS/TP or Modbus | Terminal unit controller | Older sites: temperature AI (thermistor or Pt1000) | Temperature, humidity, CO₂, occupancy and set point adjustment |
| Energy and water meters | Bus | Modbus RTU, M-Bus or BACnet | Meter gateway or controller | Pulse output DI on simple meters | kWh, kW, voltage, current, power factor, flow and volume |
| Generators and UPS | Hard-wired plus HLI | Modbus or BACnet | HVAC controller or head-end | Run, common alarm and on-load DI; mains failure DI | Fuel level, load, battery, engine data and alarms |
| Fire panel and lifts | Hard-wired, optional HLI | BACnet or vendor gateway | Monitoring only | Fire alarm and fire mode DI to plant; lift fault DI | Zone alarms and status for display; the BMS never controls fire systems |
| General sensors and actuators | Hard-wired | None | HVAC controller | Temperature, pressure, humidity and airflow AI; valve and damper actuator AO; end switches DI | None |
Rule of thumb: anything that keeps people or plant safe is hard-wired (fire shutdown, heater over-temperature, enable and stop of critical plant); everything you only need to see or trend can come over HLI. Leave 10–20% spare I/O, and get the maker’s Modbus register map or BACnet object list before you price the integration.
Common HVAC sequences
Air handling
- Start: open dampers, prove them, start fan, prove airflow, then release the valves.
- Supply temperature control with reset from return or zone demand.
- CO₂ demand ventilation: minimum outdoor air until about 800 ppm, rising to design by about 1200 ppm.
- Economy cycle and night purge when outdoor air is cool enough.
Plant
- Chiller and boiler staging on load, with lead/lag rotation by run hours.
- Variable primary or secondary pumping on differential pressure.
- Chilled water and heating water temperature reset.
Zones
- VAV boxes: airflow between minimum and maximum, reheat when cold.
- Fan coils and VRF indoor units: on/off, mode and set point, often through a gateway.
- Duct static pressure reset from the most open VAV damper.
RS-485: the wiring under MS/TP and Modbus
RS-485 (also called TIA-485 or EIA-485) only defines the electrical side: voltages, a differential signal on a twisted pair and how many devices can share it. It is not a protocol. BACnet MS/TP, Modbus RTU and others decide how the bits are framed and what they mean.
| Item | RS-232 | RS-485 |
|---|---|---|
| Connection | Point to point, two devices | Multi-drop bus: 32 standard unit loads, up to 128 or 256 with low-load transceivers |
| Signal | Single-ended, more sensitive to interference | Differential between A and B, rejects electrical noise |
| Distance | About 15 m | Up to about 1200 m at low baud rates |
| Speed | Low; for short cable runs | Up to 10 Mbps on short runs; slower the longer the cable |
| Typical use | A PC to one instrument, old serial ports | BMS field buses, drives, meters, industrial instruments |
RS-485 wiring rules
Topology
- Daisy chain or a straight bus: each device connects to the one before and the one after.
- No star, ring or tree layouts, and keep stubs (drops off the bus) very short; long branches reflect the signal and corrupt data.
- Most BMS buses are two-wire half duplex: the pair carries data one way at a time, so only one device talks at once.
Cable and termination
- Shielded twisted pair (around 24 AWG), with A and B on the same twisted pair.
- Run it away from mains and motor cables; cross them at right angles.
- Fit a 120 Ω terminating resistor at the master and at the far end only; it matters most on long or fast buses.
- Join the screens through and earth them at one point; carry a signal common where the devices have one.
Commissioning
- Every device on a bus must use the same baud rate, parity and stop bits, and a unique address.
- Some makers label the lines the opposite way round; if nothing answers, swap A and B.
- On noisy sites set the master to retry before it flags a device offline, so interference is not mistaken for a fault.
Protocols that run on RS-485
| Protocol | Where you meet it | Notes |
|---|---|---|
| Modbus RTU | Drives, meters, EC fans, generators, instruments | Master and slaves, binary frames with a CRC check. |
| BACnet MS/TP | Building automation field devices | Token passing between masters; common baud rates 9600 to 115200. |
| PROFIBUS DP | Industrial automation | Developed in Germany for distributed I/O; up to 12 Mbps. |
| DNP3 | Electricity and water utilities, SCADA | Time-stamped event data for remote monitoring and control. |
The example in the source article: paddle-wheel flow meters in a chemical dosing system report flow over RS-485 using Modbus, and the central controller stops each dose when the target volume is reached.
Protocols
| Protocol | Where you meet it | Key ideas |
|---|---|---|
| BACnet/IP | Controllers, head-ends, chillers, VRF gateways | Objects (AI, AO, BI, BO, AV, BV, multi-state, schedule, trend log, notification class) with properties; each device has a unique device instance; BBMDs pass broadcasts between IP subnets. |
| BACnet MS/TP | Room controllers, VAV, drives, field devices | RS-485 token passing, daisy chain, MAC addresses 0–127 for masters, set baud rate on every device. |
| BACnet Secure Connect (SC) | New controllers and cyber-sensitive sites | TLS-encrypted BACnet through a hub, with certificates; works across firewalls without BBMDs. |
| Modbus RTU / TCP | VSDs, meters, EC fans, generators, packaged plant | Registers rather than objects; you need the maker’s register map, scaling and data types. |
| KNX | Lighting, blinds, room control | Common in hotels and European-designed buildings; programmed with ETS. |
| M-Bus | Heat, water and gas meters | Reads many meters on one bus for billing and energy reports. |
| DALI | Lighting control | Addressable drivers and sensors; often linked to the BMS through a gateway. |
| LonWorks | Older sites | Still found in existing buildings; usually replaced or bridged during upgrades. |
Siemens building products range
Siemens Smart Infrastructure sells its building automation range under the Desigo name, with field devices, drives, fire, security and cloud products alongside. Product codes change over time; check the current Siemens catalogue before you specify.
| Family | Products | Used for |
|---|---|---|
| Desigo CC | Building management platform (head-end), with Flex Client web access | Graphics, alarms, trends, reports and integration of HVAC, lighting, power, fire and security in one station |
| Desigo Control Point | PXM30.E, PXM40.E and PXM50.E touch panels (7, 10 and 15 inch); PXG3 web interfaces | Local operation and graphics for small and medium buildings without a full head-end |
| Building X | Cloud suite: Building Operations, Energy Manager, Security Manager | Remote monitoring, analytics, energy and carbon reporting across a portfolio |
| Connect X300 | 24 V DC edge gateway | Connects existing sites and devices to Siemens cloud applications |
| Desigo PXC4 | Compact BACnet controller | Small plant: a single AHU, heat pump or pump set |
| Desigo PXC5 | Mid-size controller; PXC5.E24 with onboard I/O extendable with TX-I/O modules | AHUs, plant rooms and mixed HVAC with up to around 80 I/O per controller |
| Desigo PXC7 | High-performance controller with BACnet Secure Connect | Large plant such as chiller plants, and integration of many third-party devices |
| Earlier PXC controllers | PXC compact and modular, PXC00-E.D system controller, PXC3 room controller | Still common on existing sites you will service and upgrade |
| TX-I/O | Modular I/O modules on a TX-I/O bus | Adds digital and analogue points to a controller, mounted in the control panel |
| PXG3 routers | BACnet routers and web interfaces | Links BACnet/IP to MS/TP networks and gives web access |
| Desigo Room Automation | DXR1 and DXR2 room automation stations; QMX3 room operator units | VAV boxes, fan coils, chilled beams, with lighting and blinds by KNX or DALI |
| Climatix | OEM controllers built into packaged equipment | AHUs, rooftop units, chillers and heat pumps from equipment makers; connects to the BMS by BACnet or Modbus |
| Synco | Standalone HVAC controllers such as the Synco 700 RMU range | Small buildings and single plant items that do not need a full BMS |
| Symaro sensors | QAA room, QAM duct, QAE immersion, QAC outdoor, QAD strap-on temperature; QFM humidity; QBE and QBM pressure; QPA and QPM air quality and CO₂ | Measuring the values the controllers act on |
| Acvatix valves and actuators | Globe, ball and butterfly valves; PICV and combi valves (VPF, VPI); actuators SAT, SAY, SAX, SAV (linear) and SAL (rotary), with Modbus RTU variants | Controlling water flow to coils, heat exchangers and plant |
| OpenAir damper actuators | GDB, GLB, GMA, GCA, GBB, GIB series, with and without spring return | Outdoor air, return, mixing and VAV dampers; spring return for frost and fire positions |
| SINAMICS G120P | HVAC drive: PM230 power module with CU230P-2 HVAC control unit; about 0.75–90 kW | Fans and pumps, with built-in PID and BACnet MS/TP and Modbus RTU |
| Fire safety | Cerberus PRO and Sinteso fire detection; Sinorix extinguishing | Fire alarm systems, usually monitored by Desigo CC |
| Security | Siveillance access control and video | Access and CCTV, integrated with Desigo CC or Building X |
| Enlighted | IoT sensors fitted in light fittings | Occupancy, space use and lighting energy data |
Quoting a BMS job
Cost build-up
- Hardware: controllers, I/O modules, routers, panels, field devices (sensors, valves, actuators).
- Engineering: points list, schematics, panel drawings, submittals.
- Programming and graphics, then commissioning and witness testing.
- Cabling and installation, unless by the electrician; project management; margin.
Usual exclusions and risks
- Power supplies to panels and field devices, and cabling by others.
- IT switches, firewall and network configuration.
- Protocol cards for third-party plant, such as a chiller BACnet card or VRF gateway.
- Points not shown on the drawings, and the integrator’s licences per point or per device.
Commissioning and handover
- Point-to-pointCheck every point from the field device to the graphic: wiring, scaling and direction.
- SequencesTest each sequence, interlock and fail-safe position against the controls description.
- Alarms and trendsProve alarms reach the right people and trends are logging.
- IntegrationConfirm third-party points read and write correctly, with the right units.
- HandoverAs-built points list, schematics, backups of programs, user training and a defects-period tune-up.
Where to learn more
Courses and certifications
- Manufacturer partner training (Siemens, Honeywell, Schneider, Johnson Controls and others) for their platforms.
- Tridium Niagara 4 technical certification (TCP) for Niagara-based systems.
- BACnet International and ASHRAE resources on BACnet and control sequences (ASHRAE Guideline 36).
Practice here
- PLC programming tutorial: ladder logic, timers, interlocks and an AHU start sequence.
- Wiring bench: wire BMS controllers, drives, sensors and Modbus devices and see faults.
- Controls, drives and sensors guide for signals and wiring.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.
- Siemens: Desigo PXC controller portfolio brochure
- Siemens: Desigo PXC4, PXC5 and PXC7 datasheet
- Siemens: Desigo Control Point
- Siemens: Symaro sensors catalogue
- SINAMICS G120P data
- Siemens cloud: supported connected devices (Connect X300)
- ASHRAE Standard 135 BACnet
- BACnet International
- LORRIC: RS-485 explained in five minutes (Chinese)
- Texas Instruments: RS-232, RS-422 and RS-485 differences