Controls is the part of HVAC most people move into sideways, usually without training. Start here: what a BMS does, the three levels it is built in, points and points lists, BACnet and the other protocols, the sequences that run most plant, the Siemens range and what each part is for, and how a BMS job gets priced.

3 levelsManagement (head-end), automation (controllers) and field (sensors, actuators, drives)
DI DO AI AOThe four kinds of hard-wired points every points list is built from
BACnetThe open building automation protocol (ASHRAE 135, ISO 16484-5) most BMS tenders ask for

What a BMS does

Control

  • Starts, stops and modulates plant: AHUs, fans, pumps, chillers, boilers, heat pumps, VAV boxes and fan coils.
  • Runs control loops (PID) to hold temperature, pressure, humidity and CO₂ at set points.
  • Time schedules, holidays, after-hours buttons and optimum start.

Monitor

  • Alarms for faults, high and low values and communication loss, sent to operators by screen, email or SMS.
  • Trend logs of every important value for fault-finding and tuning.
  • Graphics showing each plant item live.

Integrate and save energy

  • Reads meters, chillers, VRF, lighting and lifts over BACnet, Modbus, M-Bus or KNX.
  • Energy reports and fault detection and diagnostics (FDD) find waste.
  • Interfaces with fire (shutdown, smoke control) and security, usually as monitored signals rather than control.

Architecture

MANAGEMENTAUTOMATIONFIELD Desigo CChead-end / SCADA PXM touch panelweb / graphics Building Xcloud, analytics IT networkswitches, VPN BACnet/IP PXC5AHU, plant+ TX-I/O PXC7chiller plantBACnet SC PXG3 routerIP ↔ MS/TP Integrationchiller, meters,VRF, lighting hard-wired I/O and BACnet MS/TP Modbus / M-Bus TCO₂ valvedamperVSDDXR2 meterchiller sensorsactuatorsdrives, roomsthird-party plant
Three levels of a typical BACnet BMS, shown with Siemens Desigo products. Other brands follow the same pattern.
System levelWhat sits thereTypical network
ManagementHead-end server and workstations, graphics, alarms, trends, reports, cloud connectionEthernet, BACnet/IP, IT network
AutomationProgrammable controllers for plant, routers, integration gatewaysBACnet/IP between controllers
FieldSensors, valves, damper actuators, drives, room controllers, metersHard-wired I/O, BACnet MS/TP, Modbus RTU, KNX, M-Bus

Points and points lists

Point typeSignalExamples
DI (digital input)Volt-free contact, open or closedFan status, fault, filter switch, fire alarm, flow switch
DO (digital output)Relay contactFan or pump enable, valve open/close, alarm lamp
AI (analogue input)0–10 V, 4–20 mA, or resistance (Pt1000, NTC)Temperatures, humidity, CO₂, duct and water pressure
AO (analogue output)0–10 V or 4–20 mAValve position, damper position, VSD speed
Software and integration pointsValues inside the controller or read over a networkSet points, schedules, occupancy, chiller and meter data over BACnet or Modbus

Count hardware points by type to size controllers and I/O modules; leave about 10–20% spare. Integration points are priced on engineering time, not hardware.

Worked example: an AHU points list

TSAIHSAITSAIHSAIVSAIMAOAIMAOAIMAIAOMAOAIDPAIDPAICDITSAIHSAISMKDICHLIDODIPSAIRA DUCTOA DUCTReturn fan: refer VSD fan pointsSupply fans: refer VSD fan pointsSPILL DUCTSA DUCTUV filterDX coilDX condensing unitAHUfilter 1filter 2
AHU system BMS control diagram: return fan, spill, return and two outdoor air dampers, two filter stages, UV lamps, a DX coil with its outdoor condensing unit and a supply fan array.
TagDevicePointsPurpose
RA TSReturn air temperature sensorAISpace temperature and economy cycle
RA HSReturn air humidity sensorAISpace humidity and enthalpy economy cycle
VSReturn air velocity or airflow stationAIReturn airflow, used to track the supply fan
Spill damperSpill air damper actuator (M)AO + AICommand and position feedback; opens with the outdoor air damper
RA damperReturn air damper actuator (M)AO + AICommand and feedback; closes as outdoor air opens
OA TSOutdoor air temperature sensorAIEconomy cycle and reset schedules
OA HSOutdoor air humidity sensorAIEnthalpy economy cycle
Max OA damperEconomy outdoor air damper actuator (M)AO + AIFree cooling with outdoor air
Min OA damperMinimum outdoor air damper actuator (M)AO + AIHolds the minimum fresh air rate
DP 1Filter 1 differential pressure sensorAIDirty filter alarm
DP 2Filter 2 differential pressure sensorAIDirty filter alarm
UV CUV filter lamp contactorDIUV lamp running status
CU COutdoor condensing unit controllerDO + DI + HLIEnable, fault and data (capacity, temperatures, alarms) over Modbus or BACnet
SA TSSupply air temperature sensorAIMain control variable for cooling
SA HSSupply air humidity sensorAIDehumidification control
SMKDuct smoke detectorDIShuts the AHU down on smoke
PSSupply duct static pressure sensorAISupply fan speed control
Each VSD fanReturn fan and each supply fanDO + AO + 2 DI + HLIRun enable, speed, run status, fault; kW, kWh and fault codes over the network
Total without fansAI 14, AO 4, DI 3, DO 1, HLI 123 pointsAdd 1 DO, 1 AO, 2 DI and 1 HLI for each VSD fan

M is the damper actuator, C a contactor or controller, TS temperature, HS humidity, VS velocity, DP differential pressure, PS static pressure, SMK smoke. Damper AI points are position feedback; keep the smoke shutdown hard-wired as well.

AHU points by type

A typical single-zone or multi-zone AHU, counted by point type. The numbers vary with the design; use them to check a points schedule or to size a controller.

TypeFull nameTypical countExamples and purpose
AOAnalogue output: valves, dampers and speed3–4Outdoor air damper position 0–100%; return, mixing or bypass damper; spill or relief damper; chilled and heating water valves (often PICVs); VSD speed reference.
AIAnalogue input: sensors and feedback8–12 or moreTemperature (TS) of outdoor, return, mixed and supply air; humidity (HS) of outdoor, return and supply air; filter differential pressure (DP) across the G4 pre-filter and F7 filter; supply static pressure or airflow (PS, VS); damper and valve position feedback.
DIDigital input: status and alarmsseveralSupply duct smoke detector (SMK, shuts the unit down); fan run status and trip; UV lamp status or fault; filter switch; fire alarm shutdown; local hand/off/auto.
DODigital output: start and stop1–2Supply and return fan start/stop; UV lamp on/off; humidifier enable.
HLIHigh-level interface over a network1 or moreEC fans, VSDs or the AHU’s own packaged controller over Modbus RTU or BACnet/IP: energy, power, current, detailed fault codes and run hours.

Filter grades G4 and F7 come from the older EN 779 standard; new specifications use ISO 16890 classes such as ePM10 and ePM1. Keep safety functions (smoke shutdown, frost protection) hard-wired even when data comes over HLI.

Points and interfaces for each plant item

Most client BMS standards split each plant item into hard-wired points for control and safety, and a high-level interface (HLI) for the extra data the equipment already has. The table is a typical arrangement; follow the project specification and the equipment maker’s points map.

EquipmentConnectionProtocolBMS interfaceHard-wired pointsHLI and network points
AHUHard-wired plus busBACnet/IP or Modbus RTUHVAC controllerSee the AHU table aboveFan energy and faults, packaged controller data
Terminal units (VAV, FCU, chilled beams)Ethernet, MS/TP or KNXBACnet/IP, BACnet MS/TP or KNXTerminal unit controllerValve (2-way or 3-way, often PICV) AO; fan speed AO or DO; damper AO; supply air temperature AIRoom temperature, humidity and CO₂ from room sensors; airflow, occupancy, set points
ChillersHard-wired plus busBACnet/IP or ModbusHVAC controller and BACnetEnable DO; run and common fault DI; chilled water set point AO; flow switch DIEntering and leaving water temperatures, compressor status and load, refrigerant pressures, refrigerant leak alarm, power and kWh, fault codes
Cooling towersHard-wired plus VSD busModbus RTUHVAC controllerFan start DO, speed AO, run and trip DI; basin high and low level DI; leaving water temperature AI; make-up and bleed valvesVSD energy and faults, conductivity from the water treatment controller
Large heat pumpsHard-wired plus busBACnet/IP or ModbusHVAC controller and BACnetEnable DO; mode DO; run and fault DI; flow and return temperature AICOP, power, refrigerant pressures, defrost status, fault codes
BoilersHard-wired plus busModbus or BACnetHVAC controllerEnable DO; flow temperature set point AO; run, lockout and fault DIFlow and return temperatures, firing rate, gas use, fault history
Pumps and fans on VSDsHard-wired for control, bus for dataModbus RTUHVAC controllerStart DO; speed AO; run and trip DI; differential pressure or flow AIFrequency, current, power, kWh, run hours, fault codes
Direct-on-line fans and pumpsHard-wiredNoneHVAC controllerStart DO; run status and trip DINone
Duct heatersHard-wired plus HLIModbus or BACnetHVAC controllerEnable DO; output AO; airflow proving and over-temperature cut-out hard-wiredPower, current, element temperature and diagnostics
VRF and split systemsGatewayBACnet/IP or Modbus gatewayMaker’s gatewayFire shutdown DI to the outdoor unit or controller where requiredOn/off, mode, set point, room temperature, fault codes for each indoor unit
Room sensorsKNX, MS/TP or ModbusKNX, BACnet MS/TP or ModbusTerminal unit controllerOlder sites: temperature AI (thermistor or Pt1000)Temperature, humidity, CO₂, occupancy and set point adjustment
Energy and water metersBusModbus RTU, M-Bus or BACnetMeter gateway or controllerPulse output DI on simple meterskWh, kW, voltage, current, power factor, flow and volume
Generators and UPSHard-wired plus HLIModbus or BACnetHVAC controller or head-endRun, common alarm and on-load DI; mains failure DIFuel level, load, battery, engine data and alarms
Fire panel and liftsHard-wired, optional HLIBACnet or vendor gatewayMonitoring onlyFire alarm and fire mode DI to plant; lift fault DIZone alarms and status for display; the BMS never controls fire systems
General sensors and actuatorsHard-wiredNoneHVAC controllerTemperature, pressure, humidity and airflow AI; valve and damper actuator AO; end switches DINone

Rule of thumb: anything that keeps people or plant safe is hard-wired (fire shutdown, heater over-temperature, enable and stop of critical plant); everything you only need to see or trend can come over HLI. Leave 10–20% spare I/O, and get the maker’s Modbus register map or BACnet object list before you price the integration.

Common HVAC sequences

Air handling

  • Start: open dampers, prove them, start fan, prove airflow, then release the valves.
  • Supply temperature control with reset from return or zone demand.
  • CO₂ demand ventilation: minimum outdoor air until about 800 ppm, rising to design by about 1200 ppm.
  • Economy cycle and night purge when outdoor air is cool enough.

Plant

  • Chiller and boiler staging on load, with lead/lag rotation by run hours.
  • Variable primary or secondary pumping on differential pressure.
  • Chilled water and heating water temperature reset.

Zones

  • VAV boxes: airflow between minimum and maximum, reheat when cold.
  • Fan coils and VRF indoor units: on/off, mode and set point, often through a gateway.
  • Duct static pressure reset from the most open VAV damper.

RS-485: the wiring under MS/TP and Modbus

RS-485 (also called TIA-485 or EIA-485) only defines the electrical side: voltages, a differential signal on a twisted pair and how many devices can share it. It is not a protocol. BACnet MS/TP, Modbus RTU and others decide how the bits are framed and what they mean.

MasterBMS / PLC Device 1addr 1 Device 2addr 2 Device Nlast on bus A+B− 120 Ω120 Ω AB screen, earthed at one point
Two-wire RS-485 bus: devices daisy-chained on one shielded twisted pair, with a 120 Ω terminator at each end and the screen earthed at one point.
ItemRS-232RS-485
ConnectionPoint to point, two devicesMulti-drop bus: 32 standard unit loads, up to 128 or 256 with low-load transceivers
SignalSingle-ended, more sensitive to interferenceDifferential between A and B, rejects electrical noise
DistanceAbout 15 mUp to about 1200 m at low baud rates
SpeedLow; for short cable runsUp to 10 Mbps on short runs; slower the longer the cable
Typical useA PC to one instrument, old serial portsBMS field buses, drives, meters, industrial instruments

RS-485 wiring rules

Topology

  • Daisy chain or a straight bus: each device connects to the one before and the one after.
  • No star, ring or tree layouts, and keep stubs (drops off the bus) very short; long branches reflect the signal and corrupt data.
  • Most BMS buses are two-wire half duplex: the pair carries data one way at a time, so only one device talks at once.

Cable and termination

  • Shielded twisted pair (around 24 AWG), with A and B on the same twisted pair.
  • Run it away from mains and motor cables; cross them at right angles.
  • Fit a 120 Ω terminating resistor at the master and at the far end only; it matters most on long or fast buses.
  • Join the screens through and earth them at one point; carry a signal common where the devices have one.

Commissioning

  • Every device on a bus must use the same baud rate, parity and stop bits, and a unique address.
  • Some makers label the lines the opposite way round; if nothing answers, swap A and B.
  • On noisy sites set the master to retry before it flags a device offline, so interference is not mistaken for a fault.

Protocols that run on RS-485

ProtocolWhere you meet itNotes
Modbus RTUDrives, meters, EC fans, generators, instrumentsMaster and slaves, binary frames with a CRC check.
BACnet MS/TPBuilding automation field devicesToken passing between masters; common baud rates 9600 to 115200.
PROFIBUS DPIndustrial automationDeveloped in Germany for distributed I/O; up to 12 Mbps.
DNP3Electricity and water utilities, SCADATime-stamped event data for remote monitoring and control.

The example in the source article: paddle-wheel flow meters in a chemical dosing system report flow over RS-485 using Modbus, and the central controller stops each dose when the target volume is reached.

Protocols

ProtocolWhere you meet itKey ideas
BACnet/IPControllers, head-ends, chillers, VRF gatewaysObjects (AI, AO, BI, BO, AV, BV, multi-state, schedule, trend log, notification class) with properties; each device has a unique device instance; BBMDs pass broadcasts between IP subnets.
BACnet MS/TPRoom controllers, VAV, drives, field devicesRS-485 token passing, daisy chain, MAC addresses 0–127 for masters, set baud rate on every device.
BACnet Secure Connect (SC)New controllers and cyber-sensitive sitesTLS-encrypted BACnet through a hub, with certificates; works across firewalls without BBMDs.
Modbus RTU / TCPVSDs, meters, EC fans, generators, packaged plantRegisters rather than objects; you need the maker’s register map, scaling and data types.
KNXLighting, blinds, room controlCommon in hotels and European-designed buildings; programmed with ETS.
M-BusHeat, water and gas metersReads many meters on one bus for billing and energy reports.
DALILighting controlAddressable drivers and sensors; often linked to the BMS through a gateway.
LonWorksOlder sitesStill found in existing buildings; usually replaced or bridged during upgrades.

Siemens building products range

Siemens Smart Infrastructure sells its building automation range under the Desigo name, with field devices, drives, fire, security and cloud products alongside. Product codes change over time; check the current Siemens catalogue before you specify.

FamilyProductsUsed for
Desigo CCBuilding management platform (head-end), with Flex Client web accessGraphics, alarms, trends, reports and integration of HVAC, lighting, power, fire and security in one station
Desigo Control PointPXM30.E, PXM40.E and PXM50.E touch panels (7, 10 and 15 inch); PXG3 web interfacesLocal operation and graphics for small and medium buildings without a full head-end
Building XCloud suite: Building Operations, Energy Manager, Security ManagerRemote monitoring, analytics, energy and carbon reporting across a portfolio
Connect X30024 V DC edge gatewayConnects existing sites and devices to Siemens cloud applications
Desigo PXC4Compact BACnet controllerSmall plant: a single AHU, heat pump or pump set
Desigo PXC5Mid-size controller; PXC5.E24 with onboard I/O extendable with TX-I/O modulesAHUs, plant rooms and mixed HVAC with up to around 80 I/O per controller
Desigo PXC7High-performance controller with BACnet Secure ConnectLarge plant such as chiller plants, and integration of many third-party devices
Earlier PXC controllersPXC compact and modular, PXC00-E.D system controller, PXC3 room controllerStill common on existing sites you will service and upgrade
TX-I/OModular I/O modules on a TX-I/O busAdds digital and analogue points to a controller, mounted in the control panel
PXG3 routersBACnet routers and web interfacesLinks BACnet/IP to MS/TP networks and gives web access
Desigo Room AutomationDXR1 and DXR2 room automation stations; QMX3 room operator unitsVAV boxes, fan coils, chilled beams, with lighting and blinds by KNX or DALI
ClimatixOEM controllers built into packaged equipmentAHUs, rooftop units, chillers and heat pumps from equipment makers; connects to the BMS by BACnet or Modbus
SyncoStandalone HVAC controllers such as the Synco 700 RMU rangeSmall buildings and single plant items that do not need a full BMS
Symaro sensorsQAA room, QAM duct, QAE immersion, QAC outdoor, QAD strap-on temperature; QFM humidity; QBE and QBM pressure; QPA and QPM air quality and CO₂Measuring the values the controllers act on
Acvatix valves and actuatorsGlobe, ball and butterfly valves; PICV and combi valves (VPF, VPI); actuators SAT, SAY, SAX, SAV (linear) and SAL (rotary), with Modbus RTU variantsControlling water flow to coils, heat exchangers and plant
OpenAir damper actuatorsGDB, GLB, GMA, GCA, GBB, GIB series, with and without spring returnOutdoor air, return, mixing and VAV dampers; spring return for frost and fire positions
SINAMICS G120PHVAC drive: PM230 power module with CU230P-2 HVAC control unit; about 0.75–90 kWFans and pumps, with built-in PID and BACnet MS/TP and Modbus RTU
Fire safetyCerberus PRO and Sinteso fire detection; Sinorix extinguishingFire alarm systems, usually monitored by Desigo CC
SecuritySiveillance access control and videoAccess and CCTV, integrated with Desigo CC or Building X
EnlightedIoT sensors fitted in light fittingsOccupancy, space use and lighting energy data

Quoting a BMS job

Cost build-up

  • Hardware: controllers, I/O modules, routers, panels, field devices (sensors, valves, actuators).
  • Engineering: points list, schematics, panel drawings, submittals.
  • Programming and graphics, then commissioning and witness testing.
  • Cabling and installation, unless by the electrician; project management; margin.

Usual exclusions and risks

  • Power supplies to panels and field devices, and cabling by others.
  • IT switches, firewall and network configuration.
  • Protocol cards for third-party plant, such as a chiller BACnet card or VRF gateway.
  • Points not shown on the drawings, and the integrator’s licences per point or per device.

Commissioning and handover

  1. Point-to-pointCheck every point from the field device to the graphic: wiring, scaling and direction.
  2. SequencesTest each sequence, interlock and fail-safe position against the controls description.
  3. Alarms and trendsProve alarms reach the right people and trends are logging.
  4. IntegrationConfirm third-party points read and write correctly, with the right units.
  5. HandoverAs-built points list, schematics, backups of programs, user training and a defects-period tune-up.

Where to learn more

Courses and certifications

  • Manufacturer partner training (Siemens, Honeywell, Schneider, Johnson Controls and others) for their platforms.
  • Tridium Niagara 4 technical certification (TCP) for Niagara-based systems.
  • BACnet International and ASHRAE resources on BACnet and control sequences (ASHRAE Guideline 36).

Practice here

  • PLC programming tutorial: ladder logic, timers, interlocks and an AHU start sequence.
  • Wiring bench: wire BMS controllers, drives, sensors and Modbus devices and see faults.
  • Controls, drives and sensors guide for signals and wiring.

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. Siemens: Desigo PXC controller portfolio brochure
  2. Siemens: Desigo PXC4, PXC5 and PXC7 datasheet
  3. Siemens: Desigo Control Point
  4. Siemens: Symaro sensors catalogue
  5. SINAMICS G120P data
  6. Siemens cloud: supported connected devices (Connect X300)
  7. ASHRAE Standard 135 BACnet
  8. BACnet International
  9. LORRIC: RS-485 explained in five minutes (Chinese)
  10. Texas Instruments: RS-232, RS-422 and RS-485 differences