A ducted heat pump is sized twice: once for the room loads and once for the duct that has to carry the air there. DuctPlan does both off the same floor plan, then turns the result into a quote.
3–5 m/sFlexible branch duct velocity in a house; above that you hear it in the bedrooms
≈1 Pa/mFriction rate the sizing works to, the same equal-friction method as commercial work
±10%How close the sum of the outlet flows should land on the indoor unit airflow
Before you start
What to have ready
- A floor plan with room names and outside wall positions, or the dimensions to draw one.
- Insulation and glazing you expect to build to, because the loads follow them.
- Where the indoor unit can physically go: ceiling space, roof space or a cupboard.
What DuctPlan is not
- It is not a full energy model. Use EnergyPlan when you need H1 or NCC compliance.
- It sizes residential and light commercial ducted systems, not VAV or chilled water plant.
- Final selection still comes from the manufacturer’s data at your design conditions.
Step by step
- Draw the planTrace the outline, drop in internal walls and name each room. Rooms need names before they can take a load.
- Set the buildingPick wall, roof and floor construction and the glazing type. These drive the room loads.
- Check the room loadsRead the heating and cooling load per room. A room that looks wrong usually has the wrong glazing area or orientation.
- Pick the indoor unitChoose a unit that covers the total load at your design conditions, then note its rated airflow.
- Place the plenum and outletsOne outlet per room for small rooms, two for long living spaces. Keep returns central and short.
- Size the ductsLet the tool size every branch, then look at the velocity column before you accept it.
- Balance and quoteAdjust outlet flows until the total matches the unit, then push the take-off into a quote.
What the tool checks for you
| Check | What it means | What to do when it flags |
|---|---|---|
| Branch velocity | Air is moving faster than the quiet limit for that duct | Go up one duct size, or split the room across two outlets |
| Total airflow | Outlet flows do not add up to the unit’s rated airflow | Rebalance the outlets, or change the unit |
| External static | The index run needs more pressure than the unit can make | Shorten the run, increase the trunk size, or pick a higher static unit |
| Room load vs outlet | A room is getting less air than its load needs | Add an outlet or move the room up the branch order |
The checks are a sanity net, not a design review. A system can pass every check and still be noisy if the unit sits over a bedroom.
Common mistakes
Sizing
- Sizing on floor area instead of the calculated load, which oversizes almost every time.
- Forgetting that an oversized unit short-cycles and dehumidifies badly.
Ductwork
- Long flexible runs pulled tight on paper and left coiled on site; the pressure loss doubles.
- Undersized returns. The return path needs as much area as the supply, and usually gets less.
Quoting
- Pricing the take-off without the access, patching and electrical work around it.
- Leaving commissioning and balancing out of the price, then doing it for free.