A ducted heat pump is sized twice: once for the room loads and once for the duct that has to carry the air there. DuctPlan does both off the same floor plan, then turns the result into a quote.

3–5 m/sFlexible branch duct velocity in a house; above that you hear it in the bedrooms
≈1 Pa/mFriction rate the sizing works to, the same equal-friction method as commercial work
±10%How close the sum of the outlet flows should land on the indoor unit airflow

Before you start

What to have ready

  • A floor plan with room names and outside wall positions, or the dimensions to draw one.
  • Insulation and glazing you expect to build to, because the loads follow them.
  • Where the indoor unit can physically go: ceiling space, roof space or a cupboard.

What DuctPlan is not

  • It is not a full energy model. Use EnergyPlan when you need H1 or NCC compliance.
  • It sizes residential and light commercial ducted systems, not VAV or chilled water plant.
  • Final selection still comes from the manufacturer’s data at your design conditions.

Step by step

  1. Draw the planTrace the outline, drop in internal walls and name each room. Rooms need names before they can take a load.
  2. Set the buildingPick wall, roof and floor construction and the glazing type. These drive the room loads.
  3. Check the room loadsRead the heating and cooling load per room. A room that looks wrong usually has the wrong glazing area or orientation.
  4. Pick the indoor unitChoose a unit that covers the total load at your design conditions, then note its rated airflow.
  5. Place the plenum and outletsOne outlet per room for small rooms, two for long living spaces. Keep returns central and short.
  6. Size the ductsLet the tool size every branch, then look at the velocity column before you accept it.
  7. Balance and quoteAdjust outlet flows until the total matches the unit, then push the take-off into a quote.

What the tool checks for you

CheckWhat it meansWhat to do when it flags
Branch velocityAir is moving faster than the quiet limit for that ductGo up one duct size, or split the room across two outlets
Total airflowOutlet flows do not add up to the unit’s rated airflowRebalance the outlets, or change the unit
External staticThe index run needs more pressure than the unit can makeShorten the run, increase the trunk size, or pick a higher static unit
Room load vs outletA room is getting less air than its load needsAdd an outlet or move the room up the branch order

The checks are a sanity net, not a design review. A system can pass every check and still be noisy if the unit sits over a bedroom.

Common mistakes

Sizing

  • Sizing on floor area instead of the calculated load, which oversizes almost every time.
  • Forgetting that an oversized unit short-cycles and dehumidifies badly.

Ductwork

  • Long flexible runs pulled tight on paper and left coiled on site; the pressure loss doubles.
  • Undersized returns. The return path needs as much area as the supply, and usually gets less.

Quoting

  • Pricing the take-off without the access, patching and electrical work around it.
  • Leaving commissioning and balancing out of the price, then doing it for free.