Plumbing and drainage

Water hot enough to kill Legionella is hot enough to scald, and much of the trade works around that one fact. What the hydraulic engineer looks after: cold and hot water, scald control, backflow prevention, foul and stormwater drainage, gas, and the valves and pipe materials that hold it together.

60 °C / 50 °C / 45 °CStore at 60 °C or above for Legionella; deliver at up to 50 °C in most buildings and 45 °C in care, school and early childhood spaces
50–500 kPa · ≤3.0 m/sUsual working pressure band at fixtures and the maximum cold-water velocity in AS/NZS 3500.1 and G12/AS1
≤0.25% leadWeighted average lead limit for copper-alloy drinking-water products in Australia and New Zealand from May 2026

Codes and lead-free rules

SubjectNew ZealandAustralia
Cold waterBuilding Code G12: G12/AS1, or G12/AS3 citing AS/NZS 3500.1PCA (NCC Vol 3) and AS/NZS 3500.1
Hot waterG12/AS1 Part 6, G12/AS2 (solar), or G12/AS3 citing AS/NZS 3500.4PCA and AS/NZS 3500.4
Sanitary plumbing and drainageG13: G13/AS1 (above ground) and G13/AS2 (below ground), or G13/AS3 citing AS/NZS 3500.2PCA and AS/NZS 3500.2
Stormwater and roof drainageE1 Surface water: E1/AS1, E1/VM1, or E1/AS2 citing AS/NZS 3500.3PCA and AS/NZS 3500.3
Backflow preventionG12/AS1, AS/NZS 2845.1 devices, AS/NZS 2845.3 field testing, specified system SS7AS/NZS 3500.1, AS/NZS 2845.1 and AS/NZS 2845.3
Lead-free drinking water fittingsG12/AS1 Amendment 14: ≤0.25% lead in copper alloys from 2 May 2026, plus DZR certificationNCC Vol 3 and WaterMark: ≤0.25% lead in copper alloys from 1 May 2026
Legionella controlAS/NZS 3666 and Building Code G12 / G4 compliance scheduleAS/NZS 3666 and state warm-water rules
Gasfitting (natural gas and LPG)AS/NZS 5601.1 under the Gas (Safety and Measurement) RegulationsAS/NZS 5601.1 and state gas regulators

Pick one compliance pathway for each system and stick with it: do not mix G13/AS1 or G13/AS2 rules with AS/NZS 3500.2 on the same drain. Check that taps, valves and fittings on drinking water carry lead-free (LF) and dezincification-resistant (DR or DZR) marks.

Cold and hot water supply

MeterRPZ / DCVbackflowtundish drainPRV≤500 kPaHot watercylinder≥60 °CPTR + ECVcirc pump ≥55 °C return60 °C flowTMV≤50 / 45 °CWC / hose tapKitchen 60 °CBasin / showercold main ≤3.0 m/s · min 50 kPa at outletStore ≥60 °C to stop Legionella · circulate ≥55–60 °C · temper personal hygiene outlets to ≤50 °C (≤45 °C care)
Potable water from the street main: meter, backflow device, pressure reducing valve, cold header, hot water cylinder with 60 °C flow-and-return loop, and thermostatic mixing to bathrooms.

Pressure and velocity

  • Minimum dynamic pressure at the furthest outlet: 50 kPa for standard taps and cisterns; commercial flush valves, sensor taps and some thermostatic mixers need 100–150 kPa.
  • Maximum static pressure at any fixture: 500 kPa. Fit a pressure reducing valve (PRV) or pressure limiting valve (PLV) where street mains or building height can push pressure past 500 kPa.
  • Maximum cold water velocity: 3.0 m/s in AS/NZS 3500.1 and G12/AS1; many specifications cap mains at 2.0–2.4 m/s and branches at 1.5–2.0 m/s to keep noise down.
  • Hot water velocity: keep flow pipes below 2.0–2.5 m/s, and pumped copper return loops below 1.0–1.2 m/s to avoid erosion-corrosion.

Simultaneous flow and head loss

  • Add up the loading units (LU) on each pipe section and read the probable simultaneous flow (L/s) from the table or curve in AS/NZS 3500.1 or G12/AS1.
  • Branch design flow is never less than the largest single fixture on that branch, and never more than all its fixtures added together.
  • Available head = minimum street pressure − meter loss − backflow loss (an RPZ drops 70–120 kPa) − static lift (9.81 kPa per metre up) − required outlet pressure.
  • Add 20–30% to straight pipe lengths as an allowance for bends, tees and valves before checking friction loss.

Tall buildings and booster pumps

  • Where street pressure cannot reach upper floors, feed a potable break tank and variable-speed booster pump set (duty/standby or triplex).
  • Split risers into pressure zones every 35–45 m of height (about 10–12 storeys) or fit floor-by-floor PRVs so the bottom floor of each zone stays below 500 kPa.
  • Fit water hammer arrestors near fast-closing solenoid valves (washing machines, dishwashers, sensor taps) and isolate risers from bedroom walls.

Hot water, Legionella and scalding

Store hot, deliver warm

  • Store domestic hot water at 60 °C or above so Legionella cannot multiply; circulated flow-and-return loops must stay at 60 °C with return water at 55 °C or above.
  • Legionella multiplies between 20 °C and 45 °C and sits dormant below 20 °C; at 60 °C about 90% die in 2 minutes, and at 70 °C almost straight away.
  • Deliver hot water at no more than 50 °C at basins, baths and showers in most buildings.
  • In early childhood centres, schools, hospitals and aged care, the limit is 45 °C through a thermostatic mixing valve (TMV to AS 4032.1), not a standard tempering valve.

Circulation, dead legs and relief valves

  • Keep uncirculated branches (dead legs) from a flow-and-return loop or heater short, under 2 L of volume, so taps run hot quickly without holding warm water.
  • Kitchen sinks, commercial dishwashers and laundry tubs can take untempered 60 °C water straight off the hot line.
  • Every unvented storage water heater needs a temperature and pressure relief (TPR) valve set at 99 °C and an expansion control valve (ECV), draining through a visible tundish to outside.
  • Lag all hot flow, return and branch pipes plus valves to NZBC H1 or AS/NZS 3500.4, and test TMV thermal shut-off every 12 months.

Fixtures, loading units and trap sizes

FixtureLoading units (LU)Flow (L/s)Discharge units (DU / FU)Min trap / wasteNotes
WC pan and cistern20.104DN80 (AU) · DN100 (NZ)Direct flush valves draw 1.2–1.5 L/s and need a DN25–DN32 cold feed.
Hand basin10.101DN32 (NZ) · DN40 (AU)Temper to ≤50 °C (≤45 °C in schools, care and hospitals via TMV).
Shower20.10–0.152DN40 · DN50WELS 3-star showerheads run at 6–9 L/min (0.10–0.15 L/s).
Domestic bath80.304DN40High draw while filling; check cylinder size and recovery.
Kitchen sink30.12–0.203DN40 · DN50Can use untempered 60 °C hot water; commercial sinks go through a grease trap.
Dishwasher (domestic)30.203DN40Usually cold-fed; fit a water hammer arrestor near the solenoid inlet.
Laundry tub30.12–0.205DN40Often takes the washing machine drain hose over a standpipe or spigot.
Washing machine30.205DN40Fast solenoid valves cause water hammer on long unclipped pipes.
Urinal1–20.05–0.151–2DN40 · DN50Uric acid scale builds up in flat pipes; keep grades steep and avoid copper wastes.
Floor waste gully (FWG)––1–3DN50 outlet (DN80/100 body)Keep the trap charged from a basin or shower waste, or fit a trap primer.
Hose tap30.20–0.25––Fit a vacuum breaker against back-siphonage.

Backflow prevention

Boundary, zone and individual

  • Boundary (containment) protection at the water meter stops site water flowing back into the council street main.
  • Zone protection isolates a group of fixtures or a plant room; individual protection sits at one piece of plant.
  • A standard check (non-return) valve is not a backflow prevention device.

Mounting and annual SS7 test

  • Mount RPZ valves horizontally 300–1500 mm above the floor with a tundish and floor drain below, because the relief port dumps water when pressures shift.
  • Never put an RPZ in a buried pit where flood water could submerge the relief port.
  • In New Zealand, testable backflow devices are Specified System SS7 on the compliance schedule and are tested every 12 months by an IQP to AS/NZS 2845.3.
Hazard ratingMeaningDevices (AS/NZS 2845.1)Typical uses
High hazardCould cause death or spread diseaseRegistered air gap (AG), reduced pressure zone device (RPZ), registered break tank (RBT)Hospitals, labs, mortuaries, cooling towers, chemical dosing, commercial kitchens, rainwater or blackwater interconnects, sprinklers with chemical additives
Medium hazardCould harm health or taint water chemically or bacteriologicallyTestable double check valve (DCV), pressure vacuum breaker (PVB)Fire hose reels, clean water sprinkler mains, boiler make-up without toxic inhibitors, pool top-up, multi-storey zone protection
Low hazardAffects taste, smell or colour onlyNon-testable dual check valve, atmospheric vacuum breaker (AVB), hose vacuum breakerDomestic hose taps, residential irrigation without fertiliser, drink dispensers, standard house meters

Sanitary plumbing and foul drainage

Open vent cowl above roofWCBasinSinkAAVtrap armDN100 stack2 × 45° base bend + no-connection zoneGraded drain DN100 min 1.65% (1:60)ORG / gully≥150 mm below fixtureBoundary IOCouncilsewerLevel 1Ground
Sanitary drainage: open roof vent, stack with base clearances, trap-arm limits or AAVs, graded underground drain, outdoor overflow relief gully (ORG) and boundary inspection opening.

Traps, vents and stack bases

  • Every fixture needs a trap with at least a 50 mm water seal (75 mm on pumped drains) to block sewer gas; P-traps and S-traps hold more water than compact bottle traps.
  • Venting keeps air pressure within ±375 Pa of atmospheric so traps do not lose their seal by siphonage or back-pressure, while drain grades hold about 0.6–0.8 m/s self-cleansing velocity.
  • Air admittance valves (AAVs to AS/NZS 4936) open on negative pressure to let air in and close by gravity; they cannot relieve positive pressure, and every drain still needs at least one open vent to outside.
  • At the bottom of a multi-storey stack, turn from vertical to horizontal with two 45° bends and a spacer, and keep branch connections clear of the base foam zone (600 mm to 2.5 m downstream and 450–1000 mm above the base).

Overflow relief gullies and gully traps

  • Every house or low-rise drain needs an outdoor relief point (an Overflow Relief Gully in Australia, or an exterior gully trap in New Zealand) so a blocked street sewer overflows outside rather than across bathroom floors.
  • Set the gully grate at least 150 mm below the lowest fixture overflow rim inside, and at least 75 mm (100 mm in unpaved ground) above finished ground so surface water stays out of the foul sewer.
  • Run at least one waste pipe (basin, shower or laundry) into the gully riser so its water seal does not dry out.

Inspection, cover, grease traps and pumps

  • Fit inspection openings (IO) or access chambers at the boundary, at bends sharper than 45°, at junctions, at stack bases and every 30 m along straight underground runs.
  • Minimum cover over buried UPVC drains: 300 mm in gardens and untrafficked ground, 450–600 mm under residential driveways, or protect shallow pipes with concrete.
  • Commercial kitchens need a council-approved grease trap sized on hourly peak flow and retention time, vented and reachable by a pump-out truck; workshops and car washes need oil and silt separators.
  • Basement fixtures below the sewer invert drain to a vented duty/standby sewage pump chamber with a macerator or vortex pump, high-level alarm, check valve and isolating valve.
Pipe sizeMinimum gradientSlope ratioMax discharge units (DU / FU)Max unvented trap armTypical use
DN322.50%1:4011.5 mSingle hand basin waste (NZ)
DN402.50%1:4022.5 mBasin, bath, kitchen sink or shower branch
DN502.50%1:4063.5 mShower, floor waste gully outlet, combined small fixtures
DN652.50%1:40154.0 mWaste branches and stacks with no WCs connected
DN801.65%1:60306.0 mMinimum WC branch in Australia; commercial floor wastes
DN1001.65%1:601806.0 mMinimum WC and house drain in NZ; main house drain in AU
DN1251.25%1:80480–Multi-unit residential and commercial collector drain
DN1501.00%1:100740–Main site collector and commercial sewer connection

Stormwater and roof drainage

Roof catchment5% AEP eaves · 1% AEP box gutterDownpipeDetention / retention tankorifice control +high-level overflowSump / silt trapDN100 min 1.0% (1:100)Secondary overland flow path (1% / 2% AEP) clear of floor slab
Roof drainage, rainwater detention tank with orifice control, silt sump and secondary overland flow path.

Design storms and roof area

  • NZ Building Code E1: carry runoff from a 10% AEP (10-year) storm without nuisance or damage, and keep a 2% AEP (50-year) storm out of houses and communal buildings (1% AEP / 100-year for commercial buildings).
  • AS/NZS 3500.3: external eaves gutters and downpipes are sized for a 5% AEP (20-year) 5-minute rainfall intensity; internal box gutters, valleys and sumps inside the building footprint are sized for a 1% AEP (100-year) storm with matching overflow.
  • Steep roofs catch wind-driven rain: in E1/AS1 the effective roof area is A_eff = A_plan × (1 + 0.5 × tan θ).

Gravity and siphonic drainage

  • Gravity downpipes run about one-third full and feed underground drains laid at minimum grades of 1.0% (1:100) for DN100, 0.5% (1:200) for DN150 and 0.4% (1:250) for DN225.
  • At 100 mm/h rainfall, gravity downpipes carry roughly 1.9 L/s for DN80 (68 m² roof), 2.3 L/s for DN90 (83 m²), 2.9 L/s for DN100 (104 m²) and 3.2 L/s for 100 × 75 mm rectangular (115 m²).
  • Siphonic roof outlets have baffles that keep air out at the design storm so pipes run 100% full under suction; collector pipes run flat under warehouse or stadium roofs to a single drop, saving deep trenches.

Detention, reuse and overland flow

  • Many councils (such as Auckland SMAF zones, Sydney and Melbourne) require on-site stormwater detention (OSD) tanks with a sized orifice plate to cap peak outflow at pre-development levels.
  • Rainwater reuse tanks feed toilets, laundry and irrigation through a pump set with mains top-up via a registered air gap or RPZ; mark non-potable pipes in lilac to AS/NZS 3500.1.
  • Keep a clear secondary overland flow path around the building so a blocked grate or 1% AEP storm runs to the street without rising over floor slabs.

Pipe materials and jointing

Material and standardServicesJointingNotes
Copper Type A / B / C (AS 1432)Cold and hot water, gas, medical gas, TPR relief drains, hot return loopsSilver brazed, capillary soldered, press-fit (V or B-press), compressionFire-proof, UV-stable and bacteriostatic; keep pumped hot return velocity ≤1.0–1.2 m/s and check water pH for pitting.
PEX (AS/NZS 2492)Concealed cold and hot water inside buildings, manifold systemsCrimp ring, sliding sleeve, cold expansion ringFlexible, quiet and few concealed joints; keep completely out of sunlight (UV degrades PEX) and clear of flues.
PP-R (ISO 15874) and PB (AS/NZS 2642)Commercial cold and hot water risers, warm water loops, house plumbingSocket heat fusion / butt fusion (PP-R); push-fit or crimp (PB)No corrosion and low heat loss; allow for thermal expansion (~0.15 mm/m·K, or ~0.035 mm/m·K for fibre-composite PP-R) with loops and guides.
PE100 (AS/NZS 4130)Buried water mains, pumped sewer rising mains, gas mains, siphonic roof drainsElectrofusion, butt fusion, mechanical compression (up to DN63)Handles ground movement well; stripe colour marks the service (blue potable, lilac recycled, yellow gas, cream/black drainage).
PVC-U DWV (AS/NZS 1260)Sanitary stacks, graded foul drains, vents, gravity stormwaterSolvent cement weld or rubber ring joint (RRJ)Smooth bore (Manning n ≈ 0.011) and low cost; wrap with acoustic lagging above ceilings and fit intumescent fire collars at fire walls and slabs.
Acoustic PP / HDPE and Cast Iron (EN 877)Apartment, hotel and hospital stacks, commercial kitchens, lab wastePush-fit EPDM socket (PP), electrofusion (HDPE), stainless couplings (cast iron)Mineral-filled 3-layer PP and cast iron cut stack noise in apartments and wards; HDPE handles 95 °C kitchen grease and lab acids.
Stainless steel 316L (AS 5200 / EN 10312)Hospitals, commercial kitchens, coastal plant rooms, high-rise risersPress-fit (M or V profile) or TIG weldedHigh pressure rating and clean bore; use EPDM O-rings for potable water and FKM (Viton) for high temperature or oils.

Valves and fittings

ItemWhat it doesNotes
Ball valveQuarter-turn full-bore isolationTight shut-off with almost no head loss; leave room for the handle and lagging.
Gate and butterfly valvesMulti-turn or geared isolation on headers (DN50 and up)Closing slowly avoids water hammer; lugged butterfly valves save space in plant rooms.
Pressure reducing valve (PRV / PLV)Drops high mains or static head pressure to ≤500 kPaFit a Y-strainer upstream and gauges both sides; use parallel big/small PRVs on commercial mains.
Thermostatic mixing valve (TMV, AS 4032.1)Blends hot and cold to 45 °C or 50 °C and shuts off if cold failsRequired for 45 °C care spaces; keep hot and cold dynamic pressures within the maker’s ratio (usually ≤2:1) and leave access for annual testing.
Tempering valve (AS 4032.2)Blends hot and cold to ≤50 °C for housesSlower wax element than a TMV; do not use where a 45 °C care limit applies.
TPR valve and expansion control valve (ECV)Protects unvented water heaters from over-temperature (99 °C) and over-pressureECV bleeds cold expansion first (~550–850 kPa); run copper relief pipe with continuous fall through a visible tundish.
Thermostatic circuit balancing valveModulates each hot return riser to hold design return temperature (e.g. 58 °C)Stops near risers short-circuiting the pump so distant risers stay hot.
Water hammer arrestor (AS 5200.007)Gas-charged diaphragm or piston cushions pressure spikes from fast valvesFit at the end of branches serving solenoid valves, washing machines, dishwashers and sensor taps.
Trap primer and mechanical trap sealKeeps floor waste traps sealed when rarely usedElectronic or pressure-drop primers drip water into floor gullies; mechanical silicone seals are only used where approved.

Natural gas and LPG (AS/NZS 5601.1)

Sizing and pressure drop

  • Add up the MJ/h rating of every gas appliance (1 kW = 3.6 MJ/h) and size each pipe section using the longest equivalent run in AS/NZS 5601.1.
  • Low-pressure natural gas is usually 1.1–2.75 kPa at the meter, with an allowable pipe pressure drop of only 0.075–0.12 kPa on 1.1 kPa supplies (or 0.15–0.25 kPa on 2.75 kPa supplies); LPG runs at 2.75 kPa after the second-stage regulator.
  • In New Zealand only authorised gasfitters may do gaswork, and the Certificate of Compliance (CoC) must name the edition of AS/NZS 5601.1 used.

Ventilation, flues and interlocks

  • Open-flued and unflued appliances need permanent high and low ventilation openings sized on total MJ/h; room-sealed balanced-flue units draw air straight from outside.
  • Keep flue terminals clear of openable windows, fresh-air intakes, gas meters, eaves and boundaries to the clearance table in AS/NZS 5601.1.
  • Commercial kitchen gas lines under exhaust hoods need an automatic gas solenoid valve interlocked with the kitchen exhaust fan, fire alarm and emergency stop button.
  • LPG is heavier than air (specific gravity 1.5–2.0): never put LPG bottles or unvented pits in basements or near drains, gullies and ignition sources.

Testing and handover

  1. Water pressure testPressure-test cold and hot water pipes before closing walls or lagging: 1500 kPa for at least 30 minutes under AS/NZS 3500.1 and G12/AS1 with no leaks.
  2. Drainage testsTest foul and stormwater drains before backfilling by water head test (1.5–3.0 m head) or low-pressure air test (35 kPa held for 3 minutes), plus CCTV camera inspection on buried mains.
  3. Flushing and disinfectionFlush drinking-water pipes at scouring velocity, clean strainers, chlorinate commercial water systems where specified, and take water samples before handover.
  4. Hot water, TMV and backflowBalance hot water return loops to 55–60 °C, log every TMV outlet temperature and cold-fail shut-off, and have an IQP certify testable backflow devices (SS7).
  5. Gas tightness and burnersManometer-test gas pipes before and after appliances are connected, purge air safely, check burner operating pressure and flue draught, and issue the gas CoC.
  6. As-builts and O&MHand over dimensioned as-built drainage drawings for the Code Compliance Certificate (CCC), with O&M manuals, valve schedules and SS7 certificates.

Formulas you use every day

QuantityFormulaUnits and notes
Flow and velocityQ = A × v × 1000Q in L/s, internal area A = π × d² ÷ 4 in m², velocity v in m/s
Static head pressureP = ρ × g × h ≈ 9.81 × hP in kPa, vertical head h in m (10 m of water = 98.1 kPa ≈ 1 bar)
Hazen–Williams friction losshf = 10.67 × L × Q¹·⁸⁵² ÷ (C¹·⁸⁵² × d⁴·⁸⁷)hf in m head (× 9.81 for kPa); Q in m³/s, ID d in m, C = 140 copper / 150 PEX and PE
Manning full-bore drain flowQ = (1 ÷ n) × A × R²/³ × S¹/² × 1000Q in L/s, hydraulic radius R = d ÷ 4 (m) full, slope S in m/m, n ≈ 0.011 for PVC-U
Rational stormwater runoffQ = C × I × A ÷ 3600Q in L/s, runoff coefficient C (1.0 for roofs), rainfall I in mm/h, effective area A in m²
Hot water heating powerP = Q × 4.18 × ΔTP in kW, water flow Q in L/s, temperature rise ΔT in K (e.g. 15 °C to 60 °C = 45 K)
Mixed water temperatureT_mix = (Q_h × T_h + Q_c × T_c) ÷ (Q_h + Q_c)Roughly 75% hot at 60 °C + 25% cold at 15 °C gives 48.8 °C tempered water
Gas appliance load1 kW = 3.6 MJ/hGas flow (m³/h) = MJ/h ÷ heating value (~38 MJ/m³ natural gas, ~95 MJ/m³ LPG)

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. MBIE: G12 Water supplies, Acceptable Solution G12/AS1 (Amendment 14, lead-free transition)
  2. MBIE: updates to plumbing and drainage compliance pathways (Build 200)
  3. MBIE: G13 Foul water Acceptable Solutions G13/AS1, G13/AS2 and G13/AS3
  4. MBIE: infiltration of surface water into the foul water system (E1 and G13)
  5. ABCB: National Construction Code Volume Three – Plumbing Code of Australia (PCA) and lead-free plumbing
  6. Standards NZ / Standards Australia: AS/NZS 3500 Plumbing and drainage series (Parts 1–4) and AS/NZS 2845 Backflow prevention
  7. Tasmania CBOS: heated water temperatures
  8. Queensland Health: Legionella and water temperature
  9. WorkSafe NZ: gas installation design and construction (AS/NZS 5601.1)
  10. Council specified system form SS7 automatic backflow prevention