Water, fire and power

Fire protection services

Fire systems are the ones that get tested for the life of the building. Sprinklers, detection and alarms, hydrants and hose reels, emergency lighting, smoke control and passive fire: what each is designed to in New Zealand and Australia, and what keeps it working afterwards.

SS1–SS15NZ specified systems: sprinklers SS1, alarms SS2, emergency lighting SS4, pressurisation SS5, emergency power SS14
90 minSix-monthly discharge test of emergency and exit lights under AS/NZS 2293.2
AS 1851Routine service of fire protection systems in Australia

Systems and standards

SystemNew ZealandAustralia
Automatic sprinklersNZS 4541 (including tall and large buildings and in-rack systems); NZS 4515 for sleeping occupancies up to 2000 m²; NZS 4517 for housesAS 2118.1
Detection and alarmsNZS 4512; NZS 4514 for smoke alarms in housesAS 1670.1
Hydrants and hose reelsSNZ PAS 4509 firefighting water supply; NZS 4510 hydrant systemsAS 2419.1 hydrants; AS 2441 hose reels
Emergency lighting and exit signsBuilding Code F6 and F8; AS/NZS 2293AS/NZS 2293
Smoke control in HVACC clauses with AS 1668.1AS 1668.1
Fire dampersAS 1682AS 1682
Penetrations and fire doorsTested to AS 1530.4 and AS 4072.1AS 1530.4, AS 4072.1, AS 1905.1

Which systems a building needs comes from the Building Code fire design (C/AS1, C/AS2 or C/VM2 in New Zealand; NCC Section E in Australia), usually written up by a fire engineer.

Sprinklers

Design

  • The hazard class (light, ordinary or high hazard, and storage height) sets the design density and the area of operation.
  • Water supply from town mains, tanks and pumps must be proved by a flow test.
  • Pipework is seismically braced (the 2020 NZ standard covers this) and every head needs clearance below obstructions.

Interfaces with other services

  • Ductwork, lights and cable trays wider than about 1.2 m need heads underneath.
  • Flow switches report to the fire alarm panel and the brigade.
  • In New Zealand, buildings with a compliant sprinkler system can be exempt from needing an evacuation scheme in some cases.

Sprinkler head types

TypeWhat it isWhere it goes
PendentHangs below the pipe and throws water down and outThe usual head in a ceiling
UprightSits above the pipe, deflector upExposed pipework in plant rooms, warehouses and car parks
SidewallMounted in a wall, throwing out across the roomCorridors, hotel rooms and anywhere a ceiling run is awkward
ConcealedA recessed head behind a flat cover plate that drops away in heatWhere the architect wants a plain ceiling
Recessed and flushPart or most of the body sits above the ceiling lineA middle ground between pendent and concealed
Dry pendent and dry sidewallAn air-filled barrel keeps water out of the head until it operatesFreezers, cool stores and unheated spaces served off a wet system
ESFREarly suppression fast response: a large high-flow head meant to put a fire out, not hold itHigh-bay racked storage, where it can replace in-rack sprinklers
In-rackHeads inside the racking itselfStorage too high or too dense for ceiling heads alone
ResidentialFast response, shaped to wet walls and keep a room survivableHouses, apartments and aged care
Extended coverageCovers more floor area per headFewer heads, but tighter rules on obstructions and spacing

Two things on the head itself are worth reading before anyone orders. Response: standard or quick, set by how thin the glass bulb is, and the two are not interchangeable in a design. And the temperature rating, shown by the bulb colour — orange and red are the low end around 57 and 68 °C, yellow and green the next step around 79 and 93 °C, with blue and mauve above that for plant rooms and kitchens. The exact values differ between standards and makers, so take them from the head’s own data sheet rather than a chart.

Detector types

TypeWhat it sensesGood atWhere it goes wrong
Photoelectric (optical) smokeLight scattered by smoke particles in a chamberSmouldering fires, which is most building firesSteam, dust and insects; it is why they sit away from bathrooms and kitchens
Ionisation smokeChange in a small ionised current as particles enterFast flaming fires with small particlesNuisance alarms from cooking, and it is being withdrawn in many markets
Multi-criteria / multi-sensorTwo or more of smoke, heat and carbon monoxide, combined in firmwareCutting false alarms while keeping sensitivityMore to commission and more to get wrong in the settings
Heat: fixed temperatureA set temperature at the detectorKitchens, plant rooms and dirty spaces where smoke detection cannot liveIt is late by definition: heat arrives after smoke
Heat: rate of riseHow fast the temperature is climbingSpaces with a normal temperature that variesA fast but harmless temperature change, such as a door opening onto hot air
Aspirating smoke detectionAir drawn through a sampling pipe network to a central very sensitive detectorData halls, heritage interiors, cold stores and high ceilingsPipe design and hole sizing are the whole job; a badly set out network detects nothing
Projected beamA beam across a space, looking for obscurationAtria, warehouses and anywhere a ceiling is too high for point detectorsBuilding movement and anything that swings through the beam
Flame: UV, IR or combinedThe radiation signature of a flame, in a direct line of sightFuel handling, turbine halls and open high-risk areasIt only sees what it can see: anything in the way blinds it
Linear heat detection cableA cable that signals where along its length it got hotCable tunnels, conveyors, car park decks and escalatorsRepair after an event, and knowing which zone the signal belongs to
Duct smoke detectorSmoke in an air handling duct, through a sampling tubeShutting an air handling unit down so it stops distributing smokeIt needs airflow to work, so it proves nothing when the fan is off

The detector is chosen by what the space does to it, not by what is cheapest. A kitchen gets heat because smoke detection will cry wolf until someone disables it, and a disabled detector is worse than the one you did not fit.

Alarms, interfaces and fire mode

Detection and alarm

  • Smoke and heat detectors, manual call points and sounders, connected to a fire panel that signals the brigade.
  • Duct smoke detectors shut down or switch HVAC plant so it does not spread smoke.
  • Voice evacuation systems are used in larger and staged-evacuation buildings.

Fire mode in mechanical services

  • Each air handling unit gets a defined action: stop, run in smoke spill, or pressurise stairs.
  • Fire and smoke dampers close or open to the fire engineer’s matrix.
  • Test the whole cause-and-effect matrix from the fire panel before handover.

Passive fire

Keeping fire cells intact

  • Every pipe, duct and cable through a fire-rated wall or floor needs a tested penetration seal.
  • Fire dampers where ducts cross fire separations, installed exactly as tested.
  • Fire doors and their frames, seals and hardware must match the tested assembly.
  • Keep a register of penetrations with photos; it is checked for the building warrant of fitness.

Keeping systems working

New Zealand

  • Fire systems are specified systems on the compliance schedule, inspected by IQPs to their standards.
  • The owner issues a building warrant of fitness (BWOF) every year.
  • Emergency lighting: monthly visual check, six-monthly 90-minute discharge test.

Australia

  • Routine service to AS 1851 at monthly, six-monthly, yearly and five-yearly intervals.
  • States have their own annual statements: for example the Annual Fire Safety Statement in NSW and essential safety measures in Victoria.

Related guides and tools

Sources

Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.

  1. MBIE: C clauses, Acceptable Solutions and Verification Methods
  2. Christchurch City Council: list of specified systems
  3. Standards NZ: NZS 4541:2020 Automatic fire sprinkler systems
  4. Codehub: NZS 4512:2021 Fire detection and alarm systems in buildings
  5. Fire and Emergency NZ evacuation scheme regulations (2021 amendment)
  6. ABCB: NCC referenced documents
  7. Council specified system sheet SS4 emergency lighting