Water, fire and power
Fire protection services
Fire systems are the ones that get tested for the life of the building. Sprinklers, detection and alarms, hydrants and hose reels, emergency lighting, smoke control and passive fire: what each is designed to in New Zealand and Australia, and what keeps it working afterwards.
Systems and standards
| System | New Zealand | Australia |
|---|---|---|
| Automatic sprinklers | NZS 4541 (including tall and large buildings and in-rack systems); NZS 4515 for sleeping occupancies up to 2000 m²; NZS 4517 for houses | AS 2118.1 |
| Detection and alarms | NZS 4512; NZS 4514 for smoke alarms in houses | AS 1670.1 |
| Hydrants and hose reels | SNZ PAS 4509 firefighting water supply; NZS 4510 hydrant systems | AS 2419.1 hydrants; AS 2441 hose reels |
| Emergency lighting and exit signs | Building Code F6 and F8; AS/NZS 2293 | AS/NZS 2293 |
| Smoke control in HVAC | C clauses with AS 1668.1 | AS 1668.1 |
| Fire dampers | AS 1682 | AS 1682 |
| Penetrations and fire doors | Tested to AS 1530.4 and AS 4072.1 | AS 1530.4, AS 4072.1, AS 1905.1 |
Which systems a building needs comes from the Building Code fire design (C/AS1, C/AS2 or C/VM2 in New Zealand; NCC Section E in Australia), usually written up by a fire engineer.
Sprinklers
Design
- The hazard class (light, ordinary or high hazard, and storage height) sets the design density and the area of operation.
- Water supply from town mains, tanks and pumps must be proved by a flow test.
- Pipework is seismically braced (the 2020 NZ standard covers this) and every head needs clearance below obstructions.
Interfaces with other services
- Ductwork, lights and cable trays wider than about 1.2 m need heads underneath.
- Flow switches report to the fire alarm panel and the brigade.
- In New Zealand, buildings with a compliant sprinkler system can be exempt from needing an evacuation scheme in some cases.
Sprinkler head types
| Type | What it is | Where it goes |
|---|---|---|
| Pendent | Hangs below the pipe and throws water down and out | The usual head in a ceiling |
| Upright | Sits above the pipe, deflector up | Exposed pipework in plant rooms, warehouses and car parks |
| Sidewall | Mounted in a wall, throwing out across the room | Corridors, hotel rooms and anywhere a ceiling run is awkward |
| Concealed | A recessed head behind a flat cover plate that drops away in heat | Where the architect wants a plain ceiling |
| Recessed and flush | Part or most of the body sits above the ceiling line | A middle ground between pendent and concealed |
| Dry pendent and dry sidewall | An air-filled barrel keeps water out of the head until it operates | Freezers, cool stores and unheated spaces served off a wet system |
| ESFR | Early suppression fast response: a large high-flow head meant to put a fire out, not hold it | High-bay racked storage, where it can replace in-rack sprinklers |
| In-rack | Heads inside the racking itself | Storage too high or too dense for ceiling heads alone |
| Residential | Fast response, shaped to wet walls and keep a room survivable | Houses, apartments and aged care |
| Extended coverage | Covers more floor area per head | Fewer heads, but tighter rules on obstructions and spacing |
Two things on the head itself are worth reading before anyone orders. Response: standard or quick, set by how thin the glass bulb is, and the two are not interchangeable in a design. And the temperature rating, shown by the bulb colour — orange and red are the low end around 57 and 68 °C, yellow and green the next step around 79 and 93 °C, with blue and mauve above that for plant rooms and kitchens. The exact values differ between standards and makers, so take them from the head’s own data sheet rather than a chart.
Detector types
| Type | What it senses | Good at | Where it goes wrong |
|---|---|---|---|
| Photoelectric (optical) smoke | Light scattered by smoke particles in a chamber | Smouldering fires, which is most building fires | Steam, dust and insects; it is why they sit away from bathrooms and kitchens |
| Ionisation smoke | Change in a small ionised current as particles enter | Fast flaming fires with small particles | Nuisance alarms from cooking, and it is being withdrawn in many markets |
| Multi-criteria / multi-sensor | Two or more of smoke, heat and carbon monoxide, combined in firmware | Cutting false alarms while keeping sensitivity | More to commission and more to get wrong in the settings |
| Heat: fixed temperature | A set temperature at the detector | Kitchens, plant rooms and dirty spaces where smoke detection cannot live | It is late by definition: heat arrives after smoke |
| Heat: rate of rise | How fast the temperature is climbing | Spaces with a normal temperature that varies | A fast but harmless temperature change, such as a door opening onto hot air |
| Aspirating smoke detection | Air drawn through a sampling pipe network to a central very sensitive detector | Data halls, heritage interiors, cold stores and high ceilings | Pipe design and hole sizing are the whole job; a badly set out network detects nothing |
| Projected beam | A beam across a space, looking for obscuration | Atria, warehouses and anywhere a ceiling is too high for point detectors | Building movement and anything that swings through the beam |
| Flame: UV, IR or combined | The radiation signature of a flame, in a direct line of sight | Fuel handling, turbine halls and open high-risk areas | It only sees what it can see: anything in the way blinds it |
| Linear heat detection cable | A cable that signals where along its length it got hot | Cable tunnels, conveyors, car park decks and escalators | Repair after an event, and knowing which zone the signal belongs to |
| Duct smoke detector | Smoke in an air handling duct, through a sampling tube | Shutting an air handling unit down so it stops distributing smoke | It needs airflow to work, so it proves nothing when the fan is off |
The detector is chosen by what the space does to it, not by what is cheapest. A kitchen gets heat because smoke detection will cry wolf until someone disables it, and a disabled detector is worse than the one you did not fit.
Alarms, interfaces and fire mode
Detection and alarm
- Smoke and heat detectors, manual call points and sounders, connected to a fire panel that signals the brigade.
- Duct smoke detectors shut down or switch HVAC plant so it does not spread smoke.
- Voice evacuation systems are used in larger and staged-evacuation buildings.
Fire mode in mechanical services
- Each air handling unit gets a defined action: stop, run in smoke spill, or pressurise stairs.
- Fire and smoke dampers close or open to the fire engineer’s matrix.
- Test the whole cause-and-effect matrix from the fire panel before handover.
Passive fire
Keeping fire cells intact
- Every pipe, duct and cable through a fire-rated wall or floor needs a tested penetration seal.
- Fire dampers where ducts cross fire separations, installed exactly as tested.
- Fire doors and their frames, seals and hardware must match the tested assembly.
- Keep a register of penetrations with photos; it is checked for the building warrant of fitness.
Keeping systems working
New Zealand
- Fire systems are specified systems on the compliance schedule, inspected by IQPs to their standards.
- The owner issues a building warrant of fitness (BWOF) every year.
- Emergency lighting: monthly visual check, six-monthly 90-minute discharge test.
Australia
- Routine service to AS 1851 at monthly, six-monthly, yearly and five-yearly intervals.
- States have their own annual statements: for example the Annual Fire Safety Statement in NSW and essential safety measures in Victoria.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.
- MBIE: C clauses, Acceptable Solutions and Verification Methods
- Christchurch City Council: list of specified systems
- Standards NZ: NZS 4541:2020 Automatic fire sprinkler systems
- Codehub: NZS 4512:2021 Fire detection and alarm systems in buildings
- Fire and Emergency NZ evacuation scheme regulations (2021 amendment)
- ABCB: NCC referenced documents
- Council specified system sheet SS4 emergency lighting