Air conditioning and air distribution
Fan selection
Most of fan selection happens before you open a catalogue. Fan laws and fan curves, forward- and backward-curved impellers, how much margin is sensible, IP ratings, and the fans built for smoke, hazardous areas, corrosive air and kitchens.
Decide these first
Duty and job
- Function: supply, exhaust, transfer, smoke spill, hazardous area or process.
- Duty point: airflow (L/s) and the system pressure at that airflow (Pa).
- Mounting: roof, wall, inline duct, ceiling, window, floor, car park or plenum.
Motor and supply
- EC (electronically commutated) or AC induction motor.
- Single-phase or three-phase supply.
- Speed control: VSD, transformer, TRIAC, or 0–10 V into an EC motor.
Site constraints
- Noise at the nearest occupied room and at the boundary.
- Size, weight, access for maintenance and lifting.
- Weather exposure, corrosion, temperature of the air moved, and budget.
Fan laws and fan curves
Fan laws
- Airflow ∝ speed; pressure ∝ speed²; power ∝ speed³.
- Example: 1440 to 1584 rpm (+10%) takes 1000 L/s at 200 Pa and 0.75 kW to 1100 L/s at 242 Pa and about 1.0 kW.
- So 5% more airflow costs about 10% more pressure and 16% more power.
Use the curve, not the laws, to select
- The fan laws only convert one fan to a new speed or impeller size.
- The real operating point is where the fan curve crosses the system curve.
- Select near peak efficiency and away from the stall region on the left of the curve.
Static, total and external pressure
- External static pressure (ESP) is what the fan must overcome outside its own casing: ducts, filters, coils and grilles.
- Check whether a curve is static or total pressure before you compare two fans.
- Galvanised duct roughness is usually taken as 0.15 mm for friction calculations.
Impellers
| Type | Where it fits | Efficiency | Watch for |
|---|---|---|---|
| Forward-curved (FC) | Small HVAC units, short ducts, low pressure and high airflow; compact and quiet at low speed | about 50–65% | Power rises with airflow, so it can overload the motor when it runs with little resistance. |
| Backward-curved (BC) or backward-inclined | Commercial and industrial systems, filters, long ducts, medium to high pressure | about 70–90% | Non-overloading power curve; larger for the same duty. |
| Axial and mixed flow | Inline exhaust, roof fans, high airflow at low to medium pressure | varies | Noisier at the same duty; blade angle sets the curve. |
Every fan type you will meet
Fans get named three different ways, and people mix all three in one sentence. The impeller says how the air is moved, the casing says how it is packaged, and the application says what it was built to survive. A “bifurcated axial” is impeller plus casing; a “kitchen exhaust fan” is an application and could be several of these.
| Family | Type | How it moves air | Pressure | Where it suits |
|---|---|---|---|---|
| Centrifugal | Forward-curved (multivane) | Many shallow blades curving towards the direction of rotation | Low to medium | Fan coils, small AHUs, packaged units: quiet and compact, but only 50–65% efficient and it overloads if the system is more open than designed |
| Centrifugal | Backward-curved / backward-inclined | Fewer, deeper blades leaning away from rotation | Medium to high | The workhorse of commercial AHUs; non-overloading, 70–85% efficient |
| Centrifugal | Airfoil | Backward-curved blades with an aerofoil section | Medium to high | The highest efficiency of the centrifugals, on clean air only: the hollow section erodes in dust |
| Centrifugal | Radial blade / paddle | Flat blades on a plain back plate, with nothing for material to lodge on | High | Dust, shavings, material handling: inefficient and noisy, but it survives |
| Centrifugal | Radial tip | A compromise between backward-curved and radial blade | High | Dust-laden air where radial blade is too inefficient |
| Centrifugal | Double inlet double width (DIDW) | Two impellers back to back on one shaft, drawing from both ends of the casing | Medium | Roughly twice the flow of the single inlet version in the same diameter; large AHUs and belt-driven plant |
| Centrifugal | Pressure blower | A narrow radial impeller spun fast, trading flow for pressure | Very high, at low flow | Combustion air, drying, air knives and anywhere a normal fan runs out of pressure |
| Centrifugal | Cabinet / acoustic box fan | A centrifugal impeller inside an insulated box with spigots on each face | Low to medium | Ceiling voids and plant rooms where the fan has to be quiet without a separate attenuator |
| Centrifugal | Plug / plenum fan | A backward-curved impeller with no scroll, blowing into a sealed plenum | Medium | Modern AHUs; almost always a direct-drive EC or PM motor, and the building block of a fan array |
| Centrifugal | In-line centrifugal (box or tube) | A centrifugal impeller in a casing with the inlet and outlet in line | Medium | Where you want centrifugal pressure but a straight duct run |
| Centrifugal | Centrifugal roof unit | A roof-mounted centrifugal, discharging up (upblast) or down (downblast) | Low to medium | Toilet and general exhaust; upblast for kitchen and anything you do not want back inside |
| Axial | Propeller / panel | A bare impeller in a ring or plate, moving a lot of air against almost nothing | Very low | Wall exhaust, condenser fans, workshop ventilation |
| Axial | Tube axial | An impeller in a close-fitting cylindrical case | Low to medium | Duct-mounted general exhaust |
| Axial | Vane axial | Guide vanes behind the impeller straighten the swirl and recover pressure | Medium to high | The efficient axial: long duct runs, tunnels, car parks |
| Axial | Bifurcated | The casing splits around a sealed pod so the motor sits out of the airstream | Low to medium | Hot, greasy, wet or contaminated air: kitchen exhaust, smoke spill, fume |
| Axial | Contra-rotating | Two impellers in series turning opposite ways | High for an axial | Where an axial has to make pressure it normally cannot, often in tunnels |
| Axial | Variable pitch | Blade angle adjustable at rest, or in some designs while running | Medium to high | Commissioning adjustment without changing the fan, and control on large installations |
| Axial | Multi-stage axial | Two or more impellers in series on one shaft, with guide vanes between | High for an axial | Mines and long tunnels, where the duty is beyond a single stage |
| Axial | Plate / wall-plate mounted | An impeller on a square plate that bolts straight into a wall opening | Very low | Workshops, plant rooms and farm buildings: the cheapest way to move a lot of air |
| Axial | Axial roof unit / cowl | An axial under a weather cowl | Very low | Roof-mounted general exhaust |
| Mixed flow | In-line mixed flow | Air leaves the impeller partly radially and partly axially | Low to medium | More pressure than an axial, quieter and more compact than a centrifugal; common in apartment and toilet exhaust |
| Cross-flow | Tangential / cross-flow | A long drum impeller; air crosses the impeller twice | Very low | Air curtains, fan coils, fan heaters: a wide even sheet of air |
| No motor | Gravity and wind-driven ventilator | A cowl, ridge vent or spinning turbine driven by wind and stack effect alone | None | Warehouse and roof relief where there is no duty to guarantee; it stops when the wind does |
| Domestic | Through-wall, through-roof and window fan | A small axial or centrifugal in a kit that penetrates one element | Very low | Bathrooms, toilets and laundries; the usual route to a compliant extract in a house |
| Domestic | Small in-line duct fan | A mixed flow or centrifugal impeller in a short duct section, hidden in the ceiling | Low | Where the grille has to be away from the fan, or one fan serves two rooms |
| Domestic | Positive input ventilation (PIV) | A roof-space or wall unit that pushes filtered air in rather than pulling stale air out | Very low | Damp and condensation in existing houses; it dilutes rather than extracts |
| Comfort | Pedestal, drum and man cooler | A propeller aimed at people rather than ducted anywhere | None | Workshops and plant rooms: it moves no heat out of the building, it just makes people feel cooler |
| Process | Cooling tower and condenser fan | Large slow propellers moving a lot of air against very little resistance | Very low | On the equipment, not in the duct: usually supplied with the tower or the chiller |
| Positive displacement | Regenerative / side channel blower | Air is dragged repeatedly through a side channel, gaining pressure each pass | High, at low flow | Pneumatic conveying, aeration, vacuum lifting |
| Positive displacement | Roots blower | Two meshing lobes trap and push a fixed volume each turn | High | Wastewater aeration and process air, not building ventilation |
The single most useful thing on this table is the difference between forward-curved and backward-curved. A forward-curved fan draws more power as the system opens up, so a filter left out or a damper left open can overload the motor. A backward-curved fan has a power curve that peaks and falls, so it cannot overload itself. That is why commercial AHUs went backward-curved and stayed there.
Fans named by the job, not the impeller
These are the names on a schedule. Each one is a duty, a certification or an environment rather than a shape, and most of them can be built on more than one impeller.
| Name | What makes it that | What to check |
|---|---|---|
| Smoke spill and high-temperature fan | Certified to keep running in hot smoke, in classes such as F200, F300 and F400: the number is degrees Celsius and the class carries a time | The class and the duration together, that the motor is out of the airstream or rated for it, and that the whole assembly including the drive and the cabling is covered, not just the fan |
| Kitchen exhaust fan | Built for grease-laden air: motor out of the airstream, drainable casing, cleanable | Upblast discharge so grease does not run back, access for cleaning, and duct velocity high enough to keep grease moving |
| Hazardous area fan | An Ex-certified motor plus a spark-resistant construction so impeller and casing cannot strike | The motor certification and the fan construction are two separate things, and both have to suit the zone and gas group |
| Corrosion-resistant fan | Fibreglass (FRP), PVC or coated steel instead of bare mild steel | What is actually in the airstream, because the right answer for one acid is wrong for another |
| Laboratory and fume cupboard exhaust | High discharge velocity to throw the plume clear of the building, often with bypass air | Discharge height and velocity against the intake positions, and what happens at low flow |
| Car park impulse and induction fan | A small high-velocity fan that pushes air along the car park instead of collecting it in ductwork | The fire mode sequence, which is usually the opposite of the ventilation mode |
| Fan array (fan wall) | Several small plug fans in a grid replacing one large fan | Redundancy and turndown are the selling points; the harmonics of many small drives are the cost |
| Air curtain | A cross-flow or centrifugal unit making a sheet of air across an opening | Height and throw against the actual door, and whether it is heated |
| HVLS / destratification fan | A very large slow ceiling fan, or a small duct fan pushing warm air back down | Warehouses and halls: it moves heat, it does not add or remove any |
| Source capture / fume extraction | An arm, hood or hose at the source rather than ventilation of the whole room | Capture velocity at the source, and where the filtered or unfiltered air ends up |
| Heat recovery unit fans | A matched supply and extract pair, almost always EC, inside the unit | They have to stay balanced, so the unit is commissioned as a pair, not as two fans |
Two of these are worth separating in your head. “Smoke spill” is a certification you can buy, with a test behind it. “Spark resistant” is a construction standard. Neither one makes a fan suitable for a hazardous area on its own, and neither replaces the other.
How a fan is packaged, arranged and driven
Two fans with the same impeller can still be different products. The casing decides how it mounts and how it is serviced, the arrangement decides where the bearings and the motor sit, and the drive decides whether you can change the speed later. All three end up on the order.
Casing formats you can order
- Scroll (housed): the classic centrifugal volute, with a flanged outlet.
- Unhoused plug or plenum: no scroll, blowing into a sealed chamber.
- Spigoted in-line box: square or tubular, inlet and outlet in line, often acoustically lined.
- Long-cased and short-cased axial: the same impeller in a long or a short tube, which changes the mounting and how much attenuation you can build in.
- Roof cowl or vertical-discharge stack, wall plate, and hinged or quick-release access versions for anything that needs cleaning.
Arrangement: where the bearings and motor sit
- The AMCA arrangement numbers describe this. Arrangement 1 has the impeller overhung with two bearings on a base and the motor separate.
- Arrangement 4 is direct drive: the impeller sits on the motor shaft and the fan has no bearings of its own.
- Arrangements 1, 3, 9 and 10 are the usual belt-drive set; 10 puts the motor inside the pedestal and is the most compact.
- Sources disagree on a few of the numbers, so take the arrangement from the maker’s own drawing rather than a table you found online.
- It matters because it decides whether the motor is in the airstream, and whether a bearing can be changed without pulling the fan out.
Drive: belt or direct
- Belt drive lets you change the speed with a pulley, which is how fans were balanced before drives were cheap.
- It also costs efficiency, needs tensioning and alignment, and sheds belt dust into the airstream.
- Direct drive removes all of that and hands speed control to the drive, which is why EC and inverter-fed direct drive took over.
- Single inlet single width (SISW) against double inlet double width (DIDW) is a third axis again: same impeller design, roughly twice the air.
When you write a fan on a schedule, four things pin it down: the duty (flow and pressure), the format (what shape it is and how it mounts), the arrangement and drive, and any certification it has to carry. Leave one out and you will get a quote for something, just not necessarily the thing you had in mind.
Who makes them
Three different kinds of supplier turn up on a fan schedule: the broad-range houses that can quote anything, the specialists who own one problem, and the component makers whose fans arrive inside somebody else’s equipment.
| Maker | Where from | What they cover | You meet them on |
|---|---|---|---|
| Systemair | Sweden, with Australian and New Zealand offices | Broad European range of fans and air handling units, including EC cabinet and in-line fans | Specified where the European range suits, and increasingly common locally |
| Woods Air Movement | United Kingdom | Axial specialists: large vane axial, contra-rotating and impulse fans | Tunnels, large car parks and smoke control |
| Soler & Palau (S&P) | Spain, sold worldwide | Very broad: in-line mixed flow and centrifugal, sidewall and tube axial, roof upblast, and residential extraction | Anything from a bathroom fan to a warehouse exhaust |
| Plymovent | Netherlands | Not a general fan house: source capture. Welding fume extraction arms, mobile and stationary filter units, spark arrestors, and vehicle exhaust extraction for fire stations and workshops | Workshops, fire stations, welding bays and plant rooms with a fume problem |
| Maskell | New Zealand, since 1968, with workshops in Auckland and Melbourne | Fibreglass engineering: FRP and PVC axial and centrifugal fans built for corrosive fume, with centrifugal sizes quoted to around 150,000 CFM | Wastewater, chemical, galvanising and anywhere mild steel would not last |
| Simx | New Zealand, part of Volution | Domestic and light commercial extraction, through-wall and through-roof fans, and heat transfer, under names including Manrose and SmartVent | Houses and small fit-outs, and the usual route to a compliant bathroom extract |
| Greenheck | United States | Very broad: roof and sidewall units, in-line, kitchen, laboratory and smoke control | Specified widely in North America, and met here through multinational designers |
| Twin City Fan | United States | Industrial process fans, tubular in-line and restaurant exhaust | Process plant rather than commercial buildings |
| Casals | Spain | Broad range including impulse fans certified for smoke at 300 and 400 degrees, and in-line smoke exhaust boxes | Car parks and smoke control |
| Sodeca | Spain | Roof fans split axial and centrifugal, with hazardous-area and high-temperature smoke versions as separate ranges | Where one family has to cover normal, Ex and smoke duties |
| Nicotra Gebhardt | Italy and Germany | Centrifugal impellers and plug fans, largely as components | Inside air handling units, like the EC makers below |
| ebm-papst | Germany | EC fans and motors, mostly as components | Inside other people’s air handling units, not usually ordered by you |
| Ziehl-Abegg | Germany | EC fans and motors, the other name on the same equipment | The same place: inside the unit |
A naming trap worth knowing: almost every maker has its own product name for car park impulse ventilation, for smoke-rated boxes and for in-line cabinets. A schedule that writes one of those product names has specified a single supplier, whether it meant to or not. Write the duty, the certification and the format instead, and let the tender find the fan.
Margins and enclosures
Safety margins
- Select for about 1.05–1.1 × the required airflow to cover duct leakage and dirty filters.
- VSD current rating at least 1.1 × motor current; 1.15–1.2 in harsh conditions.
- TRIAC controller at least 1.15–1.25 × motor current for harmonics and heat.
- Transformer controller VA at least 1.2 × voltage × current.
- Do not plan to run a standard motor above 50 Hz to make the duty.
IP ratings for outdoor fans
- IP44: sheltered outdoor locations such as under eaves.
- IP54: adds dust protection for dusty, windy sites.
- IP55 and above (IP65–66): exposed roofs and hose-down areas.
- IP67/68 is for immersion and is rarely needed for roof fans.
Special applications
Smoke spill and high temperature
- Smoke exhaust fans are tested as an assembly for a temperature and time, for example the F200, F300 and F400 classes of EN 12101-3.
- Motors use Class F (155 °C) or Class H (180 °C) insulation.
- A high-temperature rating is not a fire resistance rating (FRL) for a building element.
- Do not modify a tested smoke fan; changes void the rating.
Hazardous areas
- Classify the area to IEC 60079 (AS/NZS 60079): Zone 0, 1 or 2 for gas.
- Choose the protection type to suit: flameproof Ex d, increased safety Ex e or Ex ec.
- Spark-resistant impeller and casing materials, and earthing of the whole duct system.
Corrosive air
- Chlorine, hydrogen sulphide, chemical fumes and wastewater odour attack steel.
- Polypropylene suits laboratories: light, low cost, in standard sizes from 125 to 315 mm.
- GRP suits large wastewater systems that must last 20–30 years in continuous duty.
- Relative cost: polypropylene < GRP < 316 stainless steel.
Kitchen exhaust
- Use fans built for grease-laden air, with the motor out of the airstream.
- Duct velocity 7.6–10 m/s, sealed and fall back to the hood or grease drain.
- Access for cleaning, and a hinged roof fan base so the fan can be cleaned.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.
- Systemair New Zealand: fans
- Soler & Palau: in-line mixed flow duct fans
- Plymovent: products for clean air at work
- Maskell: industrial airflow solutions
- Simx: fan and fan kit catalogue
- ASHRAE Handbook – HVAC Systems and Equipment, Fans chapter
- EN 12101-3 Smoke and heat control systems – powered smoke and heat exhaust ventilators
- IEC 60079 Explosive atmospheres
- IEC 60529 Degrees of protection provided by enclosures (IP code)