Electric motors
Almost every moving thing in a building is a motor, and almost all of them are the same three-phase cage induction motor in a different frame. What the nameplate tells you, why star and delta both exist, how to start one without browning out the street, what the efficiency law requires here, and what changes when the area is hazardous or the supply is 11 kV.
The motors you will actually meet
| Type | How it works | Speed control | Where you meet it |
|---|---|---|---|
| Three-phase cage induction | A rotating field in the stator drags a short-circuited rotor along just behind it | VSD, or nothing at all | Fans, pumps, compressors, lifts: the default motor for everything above about 0.75 kW |
| Single-phase induction | A capacitor fakes a second phase so the field rotates; permanent-split or capacitor-start | Taps or voltage; badly, and it runs hot | Small fans, condensing units, domestic pumps |
| EC (electronically commutated) | A permanent-magnet brushless DC motor with its drive electronics built into the motor | Built in: 0–10 V, PWM or Modbus straight to the motor | AHU and FCU fans, fan arrays, heat recovery units |
| Permanent magnet synchronous (PMSM) | Magnets in the rotor lock to the stator field, so there is no slip and no rotor loss | Needs a drive, always | IE4 and IE5 pump and compressor packages, lifts |
| Synchronous reluctance (SynRM) | A shaped steel rotor with no magnets follows the field; drive and motor are sold as a pair | Needs its matched drive | IE4 and IE5 without rare-earth magnets |
| Wound rotor / slip-ring | Rotor windings brought out to slip rings, so resistance can be added while starting | Rotor resistance, historically | Old crushers, large fans on weak supplies; mostly replaced by drives |
If someone says “a motor” on a building services job and gives you no other detail, they mean a three-phase cage induction motor, four pole, foot mounted, IP55, in an aluminium or cast iron frame. Everything else gets named.
Reading the nameplate
The electrical half
- Voltage and connection together, as 400 Δ / 690 Y. The motor runs at 400 V in delta, or at 690 V in star. It is one motor with two legal ways to wire it.
- Full-load current at each voltage. This is the number the overload relay is set to, not the kW.
- Rated output in kW is shaft power out, not electrical power in. Input is kW ÷ efficiency.
- Power factor (cos φ) at full load, which falls badly at part load: a motor at 25% load may sit near 0.5.
- Efficiency and the IE class. On a modern plate the efficiency at 100, 75 and 50% load is often printed.
The mechanical half
- Speed in rpm at full load. A 4-pole 50 Hz motor says something like 1450, not 1500: the gap is the slip.
- Frame size, for example 132M. It fixes the shaft height in mm and the foot hole pattern, so frames swap between makers.
- Mounting code: B3 foot, B5 flange, B35 both, V1 vertical shaft down.
- IP rating. IP55 is the normal outdoor-capable building services motor; IP66 for washdown.
- Bearing numbers, which is the only thing anyone reads on the plate five years later.
The ratings that get ignored
- Insulation class F is normal; the temperature rise is usually limited to class B, which leaves 25 K of margin for a hot day or a bad supply.
- Duty type: S1 continuous is assumed. S2 short time and S3 intermittent are real ratings with real limits.
- Ambient and altitude. The plate assumes 40 °C and 1000 m; above either, the motor derates.
- Service factor is a North American idea. An IEC motor does not have one, and treating 1.15 as spare capacity will cook it.
Star, delta, and why both exist
A three-phase motor has three windings, and you can join them in two ways. In delta each winding sits across the full line voltage. In star the three ends are tied together, so each winding only sees line voltage divided by the square root of three. Lower voltage across the winding means less current and less torque, and that is the whole trick behind a star-delta starter.
| Star (Y) | Delta (Δ) | |
|---|---|---|
| Voltage across each winding | Line voltage ÷ √3, so 230 V on a 400 V supply | The full line voltage, 400 V |
| Line current | About one third of delta | Full |
| Starting torque | About one third of delta | Full |
| What it is used for | Running on the higher voltage, or the first step of a star-delta start | Running on the lower voltage, or the second step |
Two things go wrong with this in the field. First, a 400 V-only motor marked 400 Δ with no star rating cannot be star-delta started at 400 V, because its windings are not rated for the 690 V the star step implies: check for a 400/690 plate before you specify a star-delta starter. Second, the changeover is an open transition on most starters, so the motor briefly coasts and then reconnects out of phase, which gives a current spike that can be larger than a direct-on-line start. Closed-transition starters exist; most sites do not have them.
Starting methods
| Method | Starting current | Starting torque | Use it when | Watch for |
|---|---|---|---|---|
| Direct on line (DOL) | 6–8 × full-load current | Full, 100% | Small motors, and anything the supply can take: usually up to about 5.5 kW | Voltage dip on the board, and a mechanical slam through the drive train |
| Star-delta | About 1/3 of DOL | About 1/3, so only for unloaded or low-torque starts | Fans and unloaded pumps on a 400/690 motor | The open transition spike, and six cables to the motor instead of three |
| Autotransformer | Set by tap, typically 2–4 × | Proportional to the square of the tap voltage | Large motors where star-delta gives too little torque | Bulky, and the transformer has its own duty rating |
| Soft starter | Ramped, typically 2–4 × | Ramped with the voltage | Pumps, where you also want a controlled stop to kill water hammer | It controls voltage, not frequency: no speed control, and it must bypass once up to speed |
| Variable speed drive | About 1 × full-load current | Full torque from zero speed | Anything with a variable load, which is most fans and pumps | Bearing currents, cable length and motor derating at low speed: see the section below |
On a fan or a pump the question is usually not which starter but whether it should have a drive at all. A fan at 80% speed draws about half the power, so the drive often pays for itself before the starter argument is settled. Star-delta survives mostly on older sites and on motors too large for the supply to start direct.
Efficiency classes, and what the law here requires
IEC 60034-30-1 sets the IE classes. The class is not a single number: the minimum efficiency depends on the rating, the pole count and the frequency, so an IE3 0.75 kW motor and an IE3 90 kW motor are held to very different figures.
Australia and New Zealand
- Minimum energy performance standards for three-phase cage induction motors sit in AS/NZS 1359.5, made law through the GEMS framework in Australia and the E3 programme in New Zealand.
- The determination in force covers 0.73 kW up to but not including 185 kW, 2 to 8 poles, at IE2.
- In May 2026 ministers approved raising it: IE2 from 0.12 kW to below 0.75 kW, IE3 above that, and the scope widening to 375 kW.
- That change is approved, not yet drafted. An exposure draft of the new determination is expected around 2027, so check the current instrument before you quote a level on a tender.
- Distributors are already advertising IE3 as mandatory. On the regulator’s own documents it is not, yet.
Elsewhere
- The EU runs ahead under Regulation 2019/1781: IE3 as the floor across most of the range, with IE4 required for larger motors.
- A motor bought to EU spec will therefore pass here, but not the other way round.
What it means on a job
- Nobody has to replace a compliant installed motor because the floor moved. The rule bites on what may be supplied new.
- A higher IE class usually means a physically larger motor at the same kW, so check the frame against the base and the coupling before you swap one in.
- The efficiency gain is at full load. On a fan that spends its life at 40% speed, the drive matters far more than the IE class.
| Class | What it is called | Typically |
|---|---|---|
| IE1 | Standard efficiency | Obsolete for new three-phase motors in most markets |
| IE2 | High efficiency | What Australian and New Zealand law requires today |
| IE3 | Premium efficiency | The EU minimum, and what AU and NZ have approved moving to |
| IE4 | Super premium | Usually a permanent-magnet or synchronous reluctance machine with a drive |
| IE5 | Ultra premium | Drive-and-motor packages; about 20% less loss than IE4 |
EC motors
What they are
- A permanent-magnet brushless DC motor with the inverter built into the motor housing, so there is no separate drive on the wall.
- Single-phase or three-phase supply in, and a 0–10 V, PWM or Modbus speed signal straight to the motor.
- High efficiency across the speed range, not just at full load, which is the real reason they took over air handling.
Why HVAC went this way
- A fan array of small EC fans replaces one large belt-driven fan: no belts to tension, and the unit keeps running if one fan fails.
- Speed, run status and often power and fault codes come back over Modbus, so the BMS gets real data without extra sensors.
- Soft start is inherent, so inrush is a non-issue.
What to watch
- The electronics are the weak point and they live in the airstream. Ambient temperature and filter condition shorten their life.
- A failed EC motor is usually a whole-motor replacement, not a rewind.
- Each one is a small inverter, so a row of them puts harmonics on the board. Count them before sizing the supply.
- Check whether 0–10 V means speed or torque on that model, and whether 0 V means stopped or minimum speed.
Hazardous areas: Ex, ATEX and IECEx
If a flammable gas, vapour or dust can be present, the motor has to be built so it cannot be the ignition source. Australia and New Zealand adopt the IEC series as AS/NZS 60079, so the protection types and markings are the international ones. ATEX is the European legal framework that calls up the same technical standards, and IECEx is the international certification scheme. The letters on the plate are the same; the paperwork behind them differs.
Zones and what they mean
- Gas: Zone 0 is present continuously or for long periods, Zone 1 is likely in normal operation, Zone 2 is unlikely and short-lived if it happens.
- Dust: Zones 20, 21 and 22 follow the same pattern.
- Equipment protection level follows: Ga, Gb, Gc for gas and Da, Db, Dc for dust. A rotating machine is never Zone 0.
- Classifying the area is a separate exercise under AS/NZS 60079.10.1 for gas and .10.2 for dust, and it is not the motor supplier’s job.
Gas group and temperature class
- Group II is surface industry, subdivided IIA, IIB, IIC by how easily the gas ignites. IIC is the hardest, and a IIC motor also covers IIB and IIA.
- Group I is underground mining and is a different certification path.
- Temperature class caps the maximum surface temperature: T1 450 °C, T2 300 °C, T3 200 °C, T4 135 °C, T5 100 °C, T6 85 °C.
- It has to sit below the ignition temperature of the gas present, so the gas decides the class, not the motor.
- A plate reading Ex db IIC T4 Gb is flameproof, suits the hardest gas group, stays below 135 °C, and is good for Zone 1.
ATEX, IECEx and what applies here
- ATEX is Directive 2014/34/EU. Group II category 1 maps to Zone 0, category 2 to Zone 1 and category 3 to Zone 2, with G for gas and D for dust: a plate reading II 2G is Zone 1, gas.
- IECEx is the international scheme, and an IECEx certificate is what Australian and New Zealand practice generally works from.
- An ATEX marking alone is not automatically accepted here. Check what the site’s hazardous area dossier and the equipment schedule actually require.
- Installation, inspection and maintenance in hazardous areas is itself a competency: in Australia and New Zealand that work is restricted, and the dossier has to be kept current.
| Marking | Protection type | How it keeps you safe | Zone |
|---|---|---|---|
| Ex d | Flameproof | The explosion is allowed to happen inside a heavy enclosure whose gaps cool the escaping gas below ignition temperature | 1 and 2 |
| Ex e | Increased safety | No arcs, sparks or hot surfaces in normal service: bigger clearances, better insulation, a defined stall time (tₑ) | 1 and 2 |
| Ex de | Flameproof frame, increased-safety terminal box | The usual arrangement on a real motor, because it lets you terminate cables without opening a flamepath | 1 and 2 |
| Ex ec | Non-sparking (was Ex nA) | Built so it will not arc in normal operation, with less margin than Ex e | 2 only |
| Ex p | Pressurisation | Clean air or inert gas held above ambient pressure keeps the atmosphere out | 1 and 2, and used for large and HV machines |
| Ex t | Enclosure protection for dust | Dust is kept out and the surface temperature is limited | 21 and 22 |
The one that catches people out: an Ex e motor has a stall time tₑ on the plate, and the protection device has to disconnect it within that time from a locked rotor. That is a specified relay with a specified setting, certified with the motor, not whatever overload happened to be in the starter. Fitting a standard overload to an Ex e motor voids the protection concept even though everything looks right.
High-voltage motors
When you cross over
- Low voltage runs out somewhere around 400 to 700 kW at 400 V, because the current and the cable become absurd.
- Above that the usual steps are 3.3 kV, 6.6 kV and 11 kV, and the machine is normally bought with its switchgear and protection as a package.
- In buildings you meet these mainly on large chillers and on fire or flood pumps in big infrastructure, rarely on anything else.
What is different
- The insulation system is the product. Form-wound coils, vacuum pressure impregnation, and partial discharge testing as a condition measure rather than a pass or fail.
- Anti-condensation heaters fitted as standard, interlocked to switch on when the motor stops.
- Winding and bearing temperature by RTD, usually two per phase, wired to the protection relay.
- Sleeve or tilting-pad bearings on large machines, with forced lubrication and flow proving before start.
Starting a large machine
- The supply authority usually limits what you may do, because the starting current shows up as a voltage dip on everyone else’s supply.
- Options are a reactor or autotransformer start, a soft starter, or a drive, and the choice is often made by the network study rather than by the mechanical designer.
- Number of starts per hour is a real nameplate limit on a large machine, and exceeding it damages the rotor.
Protecting a motor
| Device | What it protects against | Notes |
|---|---|---|
| Thermal overload relay | Sustained overcurrent, and a stalled rotor | Set to the full-load current on the plate for the connection actually used. On a star-delta starter it goes in the delta leg and is set to FLC ÷ √3. |
| PTC thermistor in the windings | Actual winding temperature, including causes an overload cannot see | The only thing that catches a blocked fan cover or a motor running slowly on a drive with no airflow. |
| RTD / PT100 | Winding and bearing temperature, as a measurement not a switch | Standard on HV machines, and worth having on any motor you cannot easily get to. |
| Phase failure and asymmetry | Single phasing, which heats a motor fast and quietly | A small voltage imbalance makes a much larger current imbalance; a few percent matters. |
| Earth fault | Insulation breakdown to the frame | Core balance CT on larger motors; on a drive, use the drive’s own earth fault function. |
| Motor protection relay | All of the above, as a thermal model of the motor | Standard on anything large or important; it also logs starts, trips and running hours. |
What a drive does to a motor
Bearing currents
- Fast switching puts a common-mode voltage on the shaft. When it discharges through the bearing it pits the race, and the motor ends up with a fluted bearing and a whine.
- Fixes: a shaft grounding ring, an insulated non-drive-end bearing, or both on larger machines.
- It is a design decision at about 100 kW and above, and a known failure mode well below that.
Cable and voltage stress
- A long motor cable reflects the drive’s switching edge, and the voltage at the motor terminals can reach nearly twice the DC bus.
- Check the drive maker’s cable length limit, and fit an output filter or dV/dt reactor beyond it.
- Specify inverter-duty insulation: IEC 60034-25 for IEC motors, NEMA MG1 Part 31 for NEMA.
- Use screened motor cable, earthed at both ends through a 360° gland, or the drive will appear in other people’s signals.
Cooling and low speed
- A standard motor is cooled by a fan on its own shaft, so at 25 Hz it has roughly half the airflow and a quarter of the cooling effect.
- Constant-torque loads at low speed need a derate, or a separately powered blower.
- A fan or pump is a variable-torque load, so it derates itself and this is usually a non-issue there.
Who makes them
| Maker | Base | Known for |
|---|---|---|
| ABB | Switzerland | The broadest range, and generally reckoned the leader in low-voltage industrial motors; bought Siemens’ NEMA motor business in 2022 |
| WEG | Brazil | Motors, drives and switchgear from one maker, at keen prices; bought Regal Rexnord’s industrial motor business |
| Siemens | Germany | Second largest globally; Simotics range, and it pairs with SINAMICS drives |
| Nidec, including Leroy-Somer | Japan and France | Very large in appliance and EV motors; Leroy-Somer covers the industrial range |
| SEW-Eurodrive | Germany | Geared motors and drive packages; the default where a gearbox is part of the problem |
| Toshiba | Japan | Heavy duty and HVAC; strong in larger and high-voltage machines |
| TECO | Taiwan | Widely sold in Australia and New Zealand; good availability in standard frames |
| Wolong | China | Large volume manufacturer, frequently named among the global leaders |
| ebm-papst | Germany | EC fans and motors; the one you meet most inside air handling plant |
| Ziehl-Abegg | Germany | EC fans and motors, and the other name on the same AHU |
Frame sizes are standardised by IEC 60072, so a 132M from one maker bolts into the same holes as a 132M from another. Terminal box position, cable entry and shaft tolerance are where the surprises are, and a drive-matched motor (a PM or reluctance machine) is not interchangeable at all.
Related guides and tools
Sources
Checked October 2026. Standards and rules change; confirm the current edition before you rely on them.
- IEC 60034-30-1 Efficiency classes of line operated AC motors (IE code)
- Energy Rating AU: electric motors, and the Decision RIS on three-phase cage induction motors
- Ministers agree to strengthen energy efficiency requirements for motors (May 2026)
- EECA NZ: three-phase electric motors under the E3 programme
- CSIRO: Managing Hazardous Areas technical guide
- ATEX Directive 2014/34/EU
- IECEx international certification scheme
- ABB: motors for hazardous areas