Auxuro

Construction guide

Schools

Classrooms are full of people for hours at a time, so air quality, temperature and acoustics drive the design. State schools follow the Ministry of Education’s Designing Quality Learning Spaces (DQLS) on top of the Building Code.

800–1250 ppmTarget average CO₂ in occupied teaching spaces; never above 2000 ppm at any point in a lesson [1][2]
0.4–0.5 sReverberation time for small primary learning spaces and breakout rooms [3]
IL3Importance level for primary and secondary schools with capacity over 250 (AS/NZS 1170.0) [4]

Designing Quality Learning Spaces

Air quality and ventilation

  • Meet Building Code G4 and the DQLS requirements, whichever is more demanding [1].
  • Aim for an average of 800–1250 ppm CO₂ while occupied, with peaks never above 2000 ppm [2].
  • Mechanical systems over 500 L/s must modulate airflow automatically on measured CO₂ [1].
  • Natural ventilation needs openable windows on more than one side and controls teachers can use.

Acoustics

  • Small primary learning spaces and breakout rooms: 0.4–0.5 s reverberation time [3].
  • Small secondary learning spaces, staff rooms and libraries: 0.5–0.6 s [3].
  • Technology spaces, including music and science: 0.5–0.8 s [3].
  • Keep plant noise and rain noise on lightweight roofs in check; both count against the targets.

Thermal comfort and lighting

  • DQLS sets indoor temperature ranges for teaching time; summer overheating in glazed rooms is a common failure [2].
  • Daylight without glare: shading, high-level glazing and light shelves.
  • Heat pumps or other low-carbon heating, sized with H1-compliant envelopes.

Structure and safety

  • Schools for more than 250 are usually Importance Level 3, designed for larger earthquakes than houses [4].
  • Fire design to the Building Code C clauses, with evacuation of young children in mind.
  • Restraint of ceilings, services and partitions to NZS 4219.

How school projects run

  1. BriefThe Ministry of Education or the school board sets the roll growth and teaching model.
  2. DesignArchitect and engineers design to DQLS and the Ministry’s design standards; check each stage against DQLS.
  3. Consent and tenderBuilding consent, then tenders through the Ministry or GETS.
  4. Build in term timePlan noisy and unsafe work around the school calendar and keep children away from the site.
  5. HandoverCommission ventilation controls and CO₂ sensors and train staff; the compliance schedule and BWOF follow.

Tools for this building type

Sources

Numbers in square brackets refer to these sources, checked October 2026. Standards and rules change; confirm the current edition with your council and the issuing body before you rely on them.

  1. Ministry of Education: Ventilation for school buildings
  2. Ministry of Education: DQLS Indoor Air Quality and Thermal Comfort (v2, 2022)
  3. Ministry of Education: DQLS Acoustics (v3.1, May 2024)
  4. Building importance levels in NZ (AS/NZS 1170.0 summary)